Before Installation
DANGER
Checkup
Once a year, check the fixing brackets, the air supply and exhaust pipes and the flue terminals
to see if they need to be replaced.
WARNING
Check the Gas
Check that the rating plate indicates the correct type of gas.
Check that the gas supply line is sized for 199,900 Btuh for
the NH-2001-DV, or 150,000 Btuh for the NH-1501-DV.
Check the Power
The power supply required is 120VAC, at 60Hz.
Using the incorrect voltage may result in fire or electric shock.
Precautions on Vent Pipe Replacement
The vent system will almost certainly need to be replaced when this appliance is being installed.
Use vent pipe that is listed to UL 1738 for Category III appliances for the exhaust venting. Category
III listed vent pipe is suggested for the air supply pipe also, but other materials may be acceptable.
Consult local codes.
* If Category III listed vent pipe is already installed, check for punctures, cracks or blockages and
consult with the vent pipe manufacturer before reusing.
Use Approved Vent Materials
Use only vent materials that are listed to UL 1738 for Category III appliances for the exhaust venting
of this appliance.
Improper venting may result in fires, property damage or exposure to Carbon Monoxide.
Snow Precaution
If this product will be installed in an area where snow is known to accumulate, protect the vent
termination from blockage by snow drifts or damage from snow falling off of roofs.
CAUTION
Check Water Supply Quality
If the water supply is hard, acidic or otherwise impure, treat the water with approved methods in
order to ensure full warranty coverage.
Use the Specified Anti-Freeze
When using anti-freeze, use Noritz approved anti-freeze only.
Using an anti-freeze other than one specified by Noritz could lead to leakage of fluid (water) or
clogging of pipes.
Do Not Use Equipment for Purposes Other Than Those Specified
The NH-2001-DV/ NH-1501-DV is a boiler to be used for space heating or indirect water
heating only. Do not use the hot water supplied by the boiler for drinking purposes.
This boiler has a pressure rating of up to 150 psi, but it is designed to be used in a low pres-
sure (15 psi) closed loop heating system. Use a 30 psi relief valve.