Installation | 16
Figure 10: Distributor Location in Duct
Figure 11: Steam Distributor Above Humidifier (Copper Steam Line)
Hose cuff
with clamps
2 in. (5 cm)
min.
1 ft (30 cm)
‘P’ Trap
1 ft (30 cm)
min. before
anybend
Condensate line
Use steam hose between
cylinder and steam line.
Insulated copper
steam line. Support
so weight is not on
cylinder.
12 in.
(30 cm)
min.
Calculated absorption
distance to any obstruction
or 8-10 ft (2.4 - 3 m)
if unknown
Mount distributor
to side of duct
2 x duct
height min.
2/3 Duct
height
Note:
Refer to distributor or SAMe installation manuals for detailed installation instructions.