EasyManua.ls Logo

Nortec RH2+ - Installing the New Cylinder

Nortec RH2+
62 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Maintenance and Servicing | 44
Figure 36: Drain Valve Actuator Assembly
Installing the New Cylinder
1 Insert cylinder into drain valve. Tilt cylinder forward and fit end of steam hose to steam
outlet. Tip cylinder back into place.
2 Tighten hose clamp being careful not to over tighten and crush the plastic cylinder steam
outlet.
3 Attach color-coded cylinder plugs to the corresponding color-coded cylinder pin. Push down
completely. Connect high water sensor plug. Spring-loaded plugs should fit snuggly onto
the cylinder pin. Replace if they are loose or damaged.
4 Replace the humidifier cover and secure with two screws.
5 Turn on power to humidifier with the external disconnect.
6 Open supply water shut off valve.
7 Turn the humidifier On/Off /Drain switch to On.
Sleeve
and
Solenoid
Spring
Plunger
(Note Orientation)
CAUTION: Make sure the new cylinder is the same model as the one that was removed.
Model number is on top left corner of cylinder label.