6
not detected by the module. The TRIP LED typically
indicates if the compressor protector is open or the
compressor has no power.
The scroll compressor’s R (run), C (common), and S
(start) wires are routed through the holes in the Comfort
Alert
TM
module marked R, C, & S. NOTE: The common
wire does not need to be routed through the module for
it to operate.
Blower Time Delay Relay (Select Models)
A time delay relay may be provided with the unit and
must be installed in the indoor section. The relay will keep
the indoor blower running an additional 40 seconds for
increased cooling efficiency after the outdoor unit shuts off.
The relay has four terminals and one mounting hole.
• Connect terminal 1 to load side of blower relay.
• Connect terminal 2 to terminal R of T’stat.
• Connect terminal 3 to common terminal at blower relay
or transformer.
• Connect terminal 4 to terminal G on T’stat.
GRW
2
CEOY
Thermostat
Green
Red
Brown
G
R
W
2
Orange
Black
OY
R
C
Air Handler Heat Pump OD
Section
Typical Heat Pump with Standard Air Handler
W
2
C
W
NOTE: Jumper
between W2 and E is
required when no OD
T-Stat is used.
For 2-Stage
Heater
Kits
GRW
2
CEOY
Thermostat
Green
Red
White
G
R
Black
O Y
R
C
Air Handler Heat Pump OD
Section
Typical Heat Pump with
Outdoor Thermostat and Air Handler
W
2
C
W
E
Figure 3. Typical Thermostat Connections

• Thermostatconnectionsshouldbemadeinaccordance
with the instructions supplied with the thermostat and
the indoor equipment. A typical installation with a heat
pump thermostat and air handler is shown in Figure 3.
• Theoutdoorunitisdesignedtooperatefroma24VAC
Class II control circuit. The control circuit wiring must
comply with the current provisions of the NEC (ANSI/
NFPA 70) and with applicable local codes having
jurisdiction.
• Thelowvoltagewiresmustbeproperlyconnectedto
the units low voltage terminal block. Recommended
wire gauge and wire lengths for typical thermostat
connections are listed in Table 2.
• The thermostat should be mounted about 5 feet
above the floor on an inside wall. DO NOT install the
thermostat on an outside wall or any other location
where its operation may be adversely affected by radiant
heat from fireplaces, sunlight, or lighting fixtures, and
convective heat from warm air registers or electrical
appliances. Refer to the thermostat manufacturer’s
instruction sheet for detailed mounting and installation
information.
Table 2. Thermostat Wire Gauge
Thermostat
Wire Gauge
Recommended T-Stat Wire
Unit to T-Stat (Length in FT)
2-Wire
(Heating)
5-Wire
(Heating/Cooling)
24 55 25
22 90 45
20 140 70
18 225 110
Grounding
WARNING:
The unit cabinet must have an uninterrupted or
unbroken electrical ground to minimize personal
injury if an electrical fault should occur. Do not
use gas piping as an electrical ground!
This unit must be electrically grounded in accordance
with local codes or, in the absence of local codes, with
the National Electrical Code (ANSI/NFPA 70) or the CSA
C22.1 Electrical Code. Use the grounding lug provided in
the control box for grounding the unit.