Form O-Y P/N 273647R5, Page 1
Form O-Y (4-16)
Operation / Maintenance / Service
R-410A
Refrigerant
A
G
E
N
C
Y
P
R
O
C
E
S
S
S
T
A
R
T
-
U
P
P
R
O
D
U
C
T
C
U
S
T
O
M
E
R
W
A
R
R
A
N
T
Y
C
O
N
V
E
R
G
E
N
T
Q
U
A
L
I
T
Y
S
Y
S
T
E
M
CQS
CQS
Applies to: Models YDHA, YDMA, and YDSA
Packaged Rooftop Equipment
DANGER
This unit contains R-410A high pressure refrigerant. Hazards exist that
could result in personal injury or death. Installation, maintenance, and
service should only be performed by an HVAC technician qualied in R-410A
refrigerant and using proper tools and equipment. Due to much higher
pressure of R-410A refrigerant, DO NOT USE service equipment or tools
designed for R22 refrigerant.
IMPORTANT: Do not release refrigerant to the atmosphere! If required
service procedures include the adding or removing of refrigerant, the service
technician must comply with all federal, state and local laws. The procedures
discussed in this manual should only be performed by a qualied HVAC
technician.
Model YDHA -
High Outside
Air (Conditioned
Ventilation)
Model YDMA -
Conditioned
Makeup Air
Model YDSA -
Space
Conditioning
Obsoletes Form O-Y (11-15)

Questions and Answers

  • P
    Paul CooperAug 23, 2025
    What to do if my Nortek YDHA Air Conditioner compressor starts but cuts out on low pressure?
    • K
      Kendra GreerAug 23, 2025
      If the compressor in your Nortek Air Conditioner starts but cuts out due to low pressure, it could be due to several reasons. A low refrigerant charge is a common cause, so you should check the subcooling. Restricted airflow can also trigger this issue. Inspect for a dirty evaporator coil or filters, closed dampers, an iced evaporator coil, or an improper belt; also, check the motor amps and duct design. Another potential cause is a restriction in the refrigerant line; check the subcooling and superheat, the thermal expansion valve operation, and for any pressure drop across the filter drier. Lastly, the low pressure switch itself might be defective; check the switch (opens at 35 psi and closes at 50 psi), and if it is defective, replace it.
  • J
    Jason ChristianSep 1, 2025
    Why is my Nortek YDHA Air Conditioner head pressure too low?
    • B
      bjensenSep 1, 2025
      Low head pressure in your Nortek Air Conditioner can stem from several issues. An insufficient refrigerant charge is a common cause; check the subcooling, look for leaks, repair them, and add refrigerant. A defective or improperly adjusted expansion valve could also be the problem; check the superheat and adjust the thermal expansion valve. Low suction pressure can also lead to low head pressure. The compressor itself might be defective.
  • A
    Amanda DavisSep 3, 2025
    What causes noisy operation in Nortek YDHA units?
    • E
      Erin BergSep 3, 2025
      Noisy operation in your Nortek Air Conditioner unit can arise from various sources. Blower rotational noise might be the issue; check the blower, motor, and drive for faulty adjustment, noisy bearings, loose parts, and/or blower imbalance. Air noise can also be a factor; inspect the duct work for high air velocity. A chattering contactor could be the cause; check for adequate control voltage, shorts or breaks, and the contact points. Lastly, tubing rattle can transmit noise; dampen it by taping or clamping, and carefully bend tubing away from contact when possible.
  • D
    davidalexanderSep 5, 2025
    Why is my Nortek YDHA Air Conditioner liquid line too hot?
    • A
      amannSep 5, 2025
      If the liquid line in your Nortek Air Conditioner is too hot, it could be due to a refrigerant undercharge; check the subcooling. Another potential cause is high discharge pressure.
  • R
    Rachel KimSep 7, 2025
    Why is my Nortek YDHA running cycle is too long?
    • M
      Martha CantuSep 7, 2025
      If your Nortek Air Conditioner's running cycle is too long or the unit operates continuously, it could be due to several reasons. A refrigeration undercharge is a common cause; check the subcooling and add refrigerant. A dirty filter or evaporator coil can also lead to this issue; check the filter, coil, and airflow, and clean or replace them as needed. A dirty or clogged condenser coil can also cause this; check the coil and airflow and clean it. Air or other non-condensables in the system might be the problem; check the equalized high side pressure with the equivalent outdoor temperature. A restriction in the suction and liquid line can also cause continuous operation; check for restrictions in the refrigerant circuit. Finally, control contacts might be stuck; check the wiring.
  • X
    xmoralesSep 9, 2025
    Why is my Nortek YDHA Air Conditioner supply air temperature too low?
    • E
      Eugene ThompsonSep 10, 2025
      If the supply air temperature from your Nortek Air Conditioner is too low, it could be because the airflow is too low. Check the evaporator coil, filters, for closed dampers or grills; check the drive for loose parts, belts, or misalignment; and check the external static pressure. Another potential cause is that the return air temperature is too low; check the entering air wet bulb conditions.
  • A
    Amber AdamsSep 12, 2025
    Why does my Nortek Air Conditioner compressor short cycle?
    • B
      Brianna SteinSep 12, 2025
      If your Nortek Air Conditioner's compressor is short cycling, it could be due to an improper refrigerant charge; check the subcooling and superheat. A defective high or low pressure control can also cause this; check the high or low pressure switch. Liquid flood back is another possibility. A defective expansion valve can also lead to short cycling; check the superheat and thermal expansion valve. Poor air distribution might be the issue; check the duct work for recirculating. High discharge pressure can also cause this.
  • B
    Brandi BerrySep 14, 2025
    Why is the suction pressure high in my Nortek YDHA?
    • S
      Sean ArnoldSep 14, 2025
      High suction pressure in your Nortek Air Conditioner can be caused by a few things. There might be an excessive load on the evaporator coil; check the superheat, look for a high entering wet bulb temperature, and check for excessive air. If the compressor is unloaded, check the head pressure and thermal expansion valve. If the valve isn't functioning properly, check the pressure drop across the filter drier. Another cause could be that the expansion valve bulb isn't secured to the suction line or the valve is defective; check the thermal expansion valve, ensuring the bulb is attached properly and insulated.
  • N
    Nathaniel HubbardSep 16, 2025
    Why is the discharge pressure high in my Nortek YDHA?
    • J
      jonesstephenSep 16, 2025
      If the discharge pressure is high in your Nortek Air Conditioner, it could be due to several factors. A refrigerant overcharge is a common cause; check the subcooling and adjust the refrigerant charge accordingly. The thermal expansion valve setting might be off; check the superheat and adjust the valve as needed. If the air inlet to the condenser is dirty or obstructed, check for proper clearances and possible air recirculating. Also, a defective condenser fan motor can lead to high discharge pressure; check the condenser fan motor(s).
  • D
    dhopkinsNov 18, 2025
    Why is my Nortek Air Conditioner compressor not starting?
    • D
      Dillon MasonNov 18, 2025
      Several factors can prevent your Nortek Air Conditioner's compressor from starting. It could be due to a power issue, such as the disconnect switch being off, loose electrical connections, or an open fuse. Check these components and replace or repair as needed. Another cause might be the compressor contactor not closing; inspect the voltage to the contactor coil, transformer, slave relay, and system, replacing parts if necessary. The internal compressor thermal overload could be open; if the compressor is hot, allow it to cool for two hours. The compressor itself may be defective, indicated by an electrical failure or seizure, in which case, check the refrigerant and replace the compressor if required. Finally, a high or low pressure switch might be open or defective. If it's a manual rese...

Summary

2.0 Maintenance Requirements

2.1 Maintenance Schedule

Details the routine inspection and cleaning tasks for HVAC units, categorized by monthly and annual intervals.

3.0 Maintenance and Service Procedures - Unit & Cooling Components

3.6 Check Refrigerant Pressure and Temperatures

Procedure for checking subcooling and superheat, including important requirements and safety warnings.

3.7 Compressor Operation, Maintenance, and Replacement

Comprehensive guide on compressor handling, maintenance, oil types, replacement procedures, and system charging.

5.0 Maintenance;Service Procedures - Gas Heat Section

5.1 Gas Heat Controls

Description of gas heat controls, wiring, sequence of operation, and staging options.

6.0 Maintenance;Service Procedures - Electric Heat Section

7.0 Troubleshooting

7.1 Troubleshooting - Refrigeration

Diagnostic tables for common refrigeration circuit symptoms, probable causes, and recommended remedies.

7.2 Troubleshooting Compressor Digital Controller

Guide to interpreting LED status codes on the digital compressor controller for fault diagnosis.

7.3 Troubleshooting the Heat Section

General troubleshooting for heat sections, covering electric and gas heating system issues.

7.3.1 General Troubleshooting - Electric Heat Section

Specific troubleshooting steps for electric heat problems like no power, fan issues, or insufficient heat.

Nortek YDHA Specifications

General IconGeneral
BrandNortek
ModelYDHA
CategoryAir Conditioner
LanguageEnglish