Page 2 of 4 — DN-6985 • 04/14/05
SPECIFICATIONS
Operational Specifications
Protection range: 16 to 230 feet (5 to 70 m), 230 to 328
feet (70 to 100 m) using optional BEAMLRK kit.
Adjustment angle: ±10° horizontal and vertical. Note that
the optics move independently of the unit.
Sensitivity (6 levels):
Level 1 — 25%.
Level 2 — 30%.
Level 3 — 40%.
Level 4 — 50%.
Acclimate™ Level 5 — 30% to 50%.
Acclimate™ Level 6 — 40% to 50%.
Fault condition (trouble):
96% or more obscuration blockage.
In alignment mode.
Improper initial alignment.
Self-compensation limit reached.
Alignment aid:
Optical gunsight.
Integral signal strength indication.
Two-digit display.
Indicators:
Alarm — local red LED and remote alarm.
Trouble — local yellow LED and remote trouble.
Normal — local flashing green LED.
Test/reset features:
Integral sensitivity test filter (FSB-200S only, requires
external power supply).
Sensitivity filter (incremental scale on reflector).
Local alarm test switch.
Local alarm reset switch.
Remote test and reset switch (compatible with RTS451
and RTS451KEY test stations).
Smoke detector spacing: On smooth ceilings, 30 – 60
feet (9.1 to 18.3 m) between projected beams and not
more than one-half that spacing between a projected beam
and a sidewall. Other spacing may be used depending on
ceiling height, airflow characteristics, and response require-
ments. See NFPA 72.
REFLECTOR MOUNTING GUIDELINES
Environmental Specifications
Temperature: –22°F to 131°F (–30°C to 55°C).
Humidity: 10 – 93% RH noncondensing.
Electrical Specifications
Voltage: 15 to 32 VDC.
Average standby current (24 VDC): 2 mA maximum (LED
flashing, SLC @ 24 V).
LED current: 6.5 mA maximum.
Remote annunciator current: 11.2 mA maximum.
Average current during testing: 500 mA maximum.
Alarm current (24 VDC): 8.5 mA maximum (LED on).
Trouble/fault current
(24 VDC): 4.5 mA maximum (LED on).
Fault condition current (add to standby current): 100 mA
maximum.
Alignment mode current (24 VDC): 20 mA maximum.
External supply (FSB-200S only):
Voltage:
15 to 32 VDC.
Current:
0.5 A maximum.
Remote output (alarm):
Voltage:
15 to 32 VDC.
NOTE:
Output voltage is the same as device input voltage.
Cur-
rent:
15 mA maximum, 6 mA minimum.
NOTE: Output
current is limited by 2.2K ohm resistor.
Heater kit BEAMHK:
Voltage:
15 to 32 V.
Current:
92
mA maximum @ 32 V (heater only).
Power consumption:
nominal 1.6 W @ 24 V; maximum 3.0 W @ 32 V.
Reflector heater kit BEAMHKR:
Voltage:
15 to 32 V.
Cur-
rent:
450 mA maximum @ 32 V (per reflector).
Power con-
sumption (per reflector):
nominal 7.7 W @ 24 V; maxi-
mum 15.0 W @ 32 V.
Mechanical Specifications
Detector dimensions: 10.0" H x 7.5" W x 3.3" D (254 mm
H x 191 mm W x 84 mm D).
Reflector dimensions
for 16' to 230' (5 to 70 m) applica-
tions:
7.9" x 9.1" (200 x 230 mm).
Reflector dimensions
for applications beyond 230'/70 m:
15.7" x 18.1" (400 x 460 mm).
6985mt1.wmf