FROM PANEL OR
(+)
(-)
TO NEXT
(+)
(-)
DEVICE
(+)
(-)
(-)
(+)
3.9K EOL
RESISTOR
A2143-10
MODULE POLARITIES ARE
SHOWN IN ALARM
32 VDC MAX.
IS RECOMMENDED
BRANCH CIRCUITS
BREAK WIRE TO ENSURE
SUPERVISION OF CONNECTIONS.
DO NOT LOOP WIRE AROUND TERMINALS.
(-)
(+)
TWISTED PAIR
COMMUNICATION LINE
PREVIOUS DEVICE
(-)
(+)
TELEPHONE CONSOLE
24 VOLTS DC POWER LIMITED
9
8
7
6
5
4
3
2
1
0
0
1
2
3
4
5
6
7
8
9
TENS
ONES
ADDRESS
LOOP
0
7
8
6
5
4
3
2
1
9
10
11
12
13
14
15
TELEPHONE CONSOLE MUST
PROVIDE ITS OWN
WIRING SUPERVISION
ALL WIRING SHOWN IS SUPERVISED
AND POWER LIMITED
CONNECT MODULES TO LISTED COMPATIBLE
NOTIFIER CONTROL PANELS ONLY
FROM PANEL OR
(+)
(-)
TO NEXT
(+)
(-)
DEVICE
(+)
(-)
(-)
(+)
3.9K EOL
RESISTOR
A2143-10
MODULE POLARITIES ARE
SHOWN IN ALARM
CONNECT MODULES TO LISTED COMPATIBLE
32 VDC MAX.
IS RECOMMENDED
BRANCH CIRCUITS
BREAK WIRE TO ENSURE
SUPERVISION OF CONNECTIONS.
DO NOT LOOP WIRE AROUND TERMINALS.
ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
(-)
(+)
TWISTED PAIR
NOTIFIER CONTROL PANELS ONLY
COMMUNICATION LINE
PREVIOUS DEVICE
(-)
(+)
TELEPHONE CONSOLE
24 VOLTS DC POWER LIMITED
9
8
7
6
5
4
3
2
1
0
0
1
2
3
4
5
6
7
8
9
TENS
ONES
ADDRESS
LOOP
0
7
8
6
5
4
3
2
1
9
10
11
12
13
14
15
TELEPHONE CONSOLE MUST
PROVIDE ITS OWN
WIRING SUPERVISION
N500-69-00 2 I56-1391-02
©
2003 Notier
All relay switch contacts are shipped in the standby state (open) state, but may have transferred to the activated (closed) state during
shipping. To ensure that the switch contacts are in their correct state, modules must be made to communicate with the panel before
connecting circuits controlled by the module.
Figure 3. Typical circuit conguration, NFPA Style Y:
Figure 4. Typical fault tolerant circuit conguration, NFPA Style Z:
Relay Contact Rating: 3 Amperes maximum