UDS-4 Installation and user manual PAGE - 3
UDS-4_manu M--203.1-UDS4N-ENG Rev A.1 NOTIFIER ITALIA
Dimensions
Earthing system
The earthing system must be made in accordance with CEI and ISPELS standards and must in any case have a
resistance of less than 10 Ohm (measured at the well with the utilities disconnected). Connection of the earth cable to
the control unit is compulsory and must be made on terminal block CN1.
Degree of protection
IP30
Weight
5 Kg
2.1 - Terminal blocks
CN1
Num
Name
1
Phase
F
2
Earth
PE
3
Neutral
N
CNL
Num
Name
1
LA-
Loop A -
2
LA+
Loop A +
3
LB-
Loop B -
4
LB+
Loop B +
CNSE
Num
Name
1
Lin+
2
GND
3
Lin-
Note: All dimensions in the
figure are in millimetres.