net Installation & Commissioning Manual
11 997-448-000-2, Issue 2
July 2004
Network Configuration
If the RS485 PCB (PN: 020-479) is not fitted
in the panel and you try to configure repeaters
a fault tab is displayed. Make sure an RS485
PCB is correctly installed in any panel where
repeaters are to be configured. To clear the
FAULT tab, repeat the procedure by entering
a zero quantity for repeaters, confirm and press
RESET. Alternatively, fit an RS485 PCB and
repeat the procedure, entering the correct
number of repeaters.
Note: The RS485 PCB should only be fitted
with the panel powered down. Refer to
the ID3000 Series Installation &
Commissioning Manual (ref. 997-274).