1
nuaire.co.uk 029 2085 8400 12. 12. 17. Leaflet Number 671432
The EMC Directive
2014/30/EU
The Low Voltage
Directive
2014/35/EU
ES-ISC
Ecosmart Speed Control
Installation and Maintenance
Always handle with care to avoid damage and distortion, and where
lifting slings are employed use spreaders to ensure slings do not come
into contact with the unit case, or control pack (see fig. 2).
2.2 Dimensions (mm) & Weights (Kg)
Control sizes are selected by matching the unit full load current with
the control code i.e. control code ES-ISC3.3A is suitable for a fan with a
maximum full load current of 3.3A.
The Inverter overload is pre-set at the rating plate value, if a lower
setting is required fit an appropriately sized overload relay to the output
contactor and adjust accordingly.
1.0 INTRODUCTION
ES-ISC Ecosmart Controls
The Ecosmart Energy Saving Speed
Control is designed to control selected
Nuaire fans and to match the range of
integrated Ecosmart control systems.
The control is only available for
three phase electrical supply.
The case material is of Aluzinc corrosion
resistant steel, incorporates a frequency
inverter, Ecosmart control board and is
directly compatible with the Ecosmart
range of user controls, time clocks, ‘stats
and sensors.
Figure 1. Ecosmart Speed
Control
2.0 DELIVERY & RECEIPT OF EQUIPMENT
All equipment is inspected prior to despatch and leaves the factory in
good condition. Upon receipt of the equipment an inspection should be
made and any damage indicated on the delivery note.
Particulars of damage and/or incomplete delivery should be endorsed
by the driver delivering the goods before offloading by the purchaser.
No responsibility will be accepted for damage sustained during the
offloading from the vehicle or on the site thereafter.
All claims for damage and/or incomplete delivery must be reported to
Nuaire within two days of receipt of the equipment.
2.1 Offloading & Handling
The weight of the unit modules and palletised items are displayed on
the packaging.
Some of the modules have an uneven weight distribution, and this will
be indicated by labelling where appropriate.
Offloading and positioning of the equipment is the responsibility of
the purchaser. Items should only be lifted by competent personnel
following appropriate risk assessment.
Assembly with
base frame
Palletised
Forklift
Slings via spreaders fitted to unit
with base frame.
Please note that above images are
examples of typical lifting methods.
Actual unit lifting plan and risks
must be assessed by competent
personnel before moving the unit.
Figure 2. Typical
lifting methods.
Unit Code A B C Weight
Drill Pattern
D E
ES-ISC1.2A 230 325 410 6 340 298
ES-ISC2.4A 230 325 410 6 340 298
ES-ISC3.3A 230 325 410 6 340 298
ES-ISC4.1A 230 325 410 6 340 298
ES-ISC5.6A 290 390 455 14 470 373
ES-ISC7.3A 290 390 455 14 470 373
ES-ISC8.8A 290 390 455 14 470 373
ES-ISC12.5A 290 390 455 20 470 373
ES-ISC15.6A 290 390 455 20 470 373
ES-ISC23.1A 290 390 455 20 470 373
ES-ISC38.0A 355 525 805 40 710 510
3.0 INSTALLATION
The installation must be carried out by competent personnel in
accordance with the appropriate authority and conforming to all
statutory and governing regulations i.e. IEE, CIBSE, HVCA etc.
The Ecosmart control is desgined to be installed indoors, away from
any water spray or steam generating source. Fix or mount in upright
position to a secure vibration free vertical surface (see fig. 1 & 3). Ensure
the ventilation grilles are free of obstruction.
If the unit is installed outdoors, the matching size weathering cover
ES-ISC-WP* must be used to provide weather protection.
E
A
C
D/2
D/2
B
D
Figure 3. Dimensions and drill pattern.