DESCRIPTION
The nVent RAYCHEM EC-TS electronic thermostat is an
ambient, pipe, or slab sensing thermostat that is ideal for pipe
freeze protection, flow maintenance, freezer frost heave and
floor heating and snow melting applications. The EC-TS can
be used to control a single heat-tracing circuit or as a pilot to
control a contactor switching multiple heat-tracing circuits.
Thetemperature set point can be visually checked through the
clear lid, as can the LED indicators for alarm, power and heating
cable status. The stainless steel sensor makes it an ideal
thermostat for applications that require an embedded sensor.
The set point range for these thermostats is between 30°F
(–1°C) and 110°F (43°C). It operates at voltages between 100 to
277 Vac and switches current to 30 Amps.
For technical support call nVent at (800)545-6258.
TOOLS REQUIRED
Large slotted screwdriver Needle nose pliers
Small slotted screwdriver
ADDITIONAL MATERIALS REQUIRED
Appropriate mounting fasteners
MI cable grounding kit (for direct connection of Pyrotenax
heating cables) Catalog No: MI-GROUND-KIT
This component is an electrical device that must be
installed correctly to ensure proper operation and to
prevent shock or fire. Read these important warnings
and carefully follow all of the installation instructions.
To minimize the danger of fire from sustained
electrical arcing if the heating cable is damaged
or improperly installed, and to comply with the
requirements of nVent, agency certifications,
and the National Electrical Code, ground-fault
equipment protection must be used. Arcing may
not be stopped by conventional circuit breakers.
Component approvals and performance are based
on the use of nVent-specified parts only. Do not
use substitute parts or vinyl electrical tape.
The black heating cable core and fibers are
conductive and can short. They must be
properly insulated and kept dry.
Damaged bus wires can overheat or short. Do
not break bus wire strands when scoring the
jacket or core.
Keep components and heating cable ends dry
before and during installation.
Use only fire resistant insulation materials, such
as fiberglass wrap or flame-retardant foam.
WARNING:
KIT CONTENTS
Item Qty Description
A 1 Lid
B 1 Wire cover
C 1 Box with electronics
D 1 25 foot temperature sensor
E 1 MI cable grounding kit (P000000279)
F 1 Pipe support bracket (optional; 707366)
B
A
D
C
E
F
APPROVALS
EC-TS
Ambient, Pipe or Slab Sensing Electronic Thermostat With
25 Foot Temperature Sensing Lead Installation Instructions
Question and Answer IconNeed help?

Do you have a question about the nvent EC-TS and is the answer not in the manual?

nvent EC-TS Specifications

General IconGeneral
Brandnvent
ModelEC-TS
CategoryThermostat
LanguageEnglish

Summary

Product Overview and Requirements

Product Description

Details the EC-TS thermostat for pipe freeze, flow maintenance, and floor heating applications.

Kit Contents

Lists all components included in the EC-TS thermostat kit for installation.

Tools and Additional Materials

Specifies required tools and optional or necessary additional materials for installation.

Important Safety Warnings

Installation Procedures

Enclosure Mounting

Instructions for attaching the thermostat enclosure to the wall using mounting fasteners.

Heating Cable Connection Methods

Details connecting heating cables either via a junction box or directly.

Connecting Incoming Power

Guidance on connecting the power and ground wires to the terminal block.

Preparing and Placing the Sensor

Steps for preparing the sensor lead wire and placing it for ambient or pipe/slab applications.

Connecting the Sensor Wires

Instructions for inserting sensor wires into the terminal block, matching colors.

Completing the Installation

Final steps including installing the wire cover, setting the pointer, and installing the lid.