FEEDDEL. = After ignition, the feed auger start can be delayed to
(Fuel feeding delay) allow proper fuel kindling and burning out (suitable
for hard fuel like pellets).
RE-INGN. = Should normally be set to 1.
(No. of re-ignition attempts)
AFT.FEED = After the thermostat has cut out and fan after-blo
(After-feeding by auger) wing time is up, you can let the feed auger run a little
longer (normally about 10 sec.). is is allowed only if
the burner feeding auger comes directly from the main
fuel storage. If not, this value must be 0.
ADD.AUG. Applies to chip burners only, not to pellets burners!
(Additional auger) = Function for two or more feed augers. In this case
the auger right by the burner is connected to its own
terminals. When the thermostat cuts out, the au
ger continues running, emptying itself. Mode 0 is
not used; mode 1 = Normal operation; mode 2 = Ad
ditional auger runs during the ignition process; mode
3 = Additional auger follows the main auger when
feeding at intervals.
AUG.AFT. Applies to chip burners only, not to pellets burners!
(After-feeding by add. auger) = Desired after-feeding by the additional auger after
the thermostat has cut out (normally about 90 sec.).
DARK = Photocell sensitivity, factory-adjusted to 120.
LIGHT = Photocell sensitivity, factory-adjusted to 80.
S. START (Soft start) = For pellets burners this should be set to 1.
THM.DEL. = To be used for hot-water tanks. Here you can pro
(ermostat delay) long the burner’s idle time by 15–360 minutes.
IDLETIME = Should always be set to 30 sec.
PLEASE NOTE: is control program is part of a patented burner, whose software is included
in the patent. Copying without our permission will be subject to legal action.