Using cooling functions
Master Settings Factory settings
BA/FS
Cooling mode Day cooling temperature Day heat temperature + 3°C
Night cooling temperature Day cooling temperature + 3°C
DEW point safety zone DEW point + 3°C
Room temperature control PI - control P = 4°C
I = 90-180 sec
K-factor = 0.1
Floor Limit temperature control P - control P = 4°C
Adaptive PWM control Max allowed Room temperature fl uctuation +/- 0.5°C
Self adjusting (adaptive) PWM time interval limits 15 – 45 minutes
Max number of connected
sensors
Wired and wireless 24
Sensor timeouts Wired 300 sec. (5 min)
Wireless 10000 sec. (2h 45 min)
FS
Minimum cooling supply water temperature 16°C
Supply water temperature
control
PI - control P = 20°C
I = 300 sec.
K-factor = 0.05