Technical Specifications
BS-1634
4 zone fire
detection panel
BS-1636
6 zone fire
detection panel
Mains power supply 220-240V AC / 50-60Hz
Two 12V Lead acid sealed 2.6Ah
Stabilized power supply 27.6V / max. 400mA
Two 24V circuits that are monitored for open and short circuit conditions
(maximum current 300mA each). Each output is protected
with a self-reseting electronic fuse.
24VDC ( ±3VDC) permanent output with maximum current output 0.3 A
The output is protected with a self-reseting electronic fuse.
ABS - polycarbonate
Consumption
Battery type
Charging circuit
Zone circuits
Alarm circuits
Output 24P
Construction material
2 circuits monitored for
short and open circuit
conditions (maximum current 35mA)
24VDC ( ±3VDC) reset interrupted output with maximum current output 0.3 A
The output is protected with a self-reseting electronic fuse.
Output 24M
Three relays contacts are rated at 30VDC and 5A maximum
each. Under no circumstances should voltages or currents outside limits
be connected. All relays output must be protected with a fuse of the same rating.
Outputs Relays
325 x 240 x 85 mm
ΕΝ 54-2, ΕΝ 54-4
2 years
Dimensions
Weight
Produced in accordance to
Guarantee
Up to 95% relative humidity
Humidity
o
0 to 50 C
Operation temperature
The total output current ( zones circuits, siren circuit, outputs 24P, 24M)
must not exceed 600mA.
(ImaxA = ImaxB = 600mA, Imin = 30mA)
Total load
IP30
1Ohm
900mA
21V
Cables for fire rated cables systems such a FIP200,MICC, PYROFIL
The panel has only one serviceable fuse to protect incoming mains supply.
This fuse is 630 must be replaced with a fuse T mAL250V
of the same type and rating
IP
Battery maximum internal
resistance Rimax
Battery cut of voltage
Maximum current
batteries discharge
Cables
Fuse ratings
4 circuits monitored for
short and open circuit
conditions (maximum current 35mA)
6 circuits monitored for
short and open circuit
conditions (maximum current 35mA)
50VA
Autonomy
72 hours (Maximum connected detectors 72 and
no load at output 24VM and 24VP)
BS-1632
2 zone fire
detection panel
921163600_09_022
1360gr (3080gr with battery) 1350gr (3070gr with battery) 1345gr (3065gr with battery)