2-8
Measuring Input Wiring
–
–
DC voltage
1-5V
ON/OFF
Extension leadwire
DC current
Shunt resistor
–/Bb +/A –/Bb +/A
–/Bb +/A –/Bb +/A
++
Thermocouple input Resistance temperature detector input
DC voltage input, 1-5V input, 
and ON/OFF input
DC current input
Leadwire resistance: 
10 Ω max./wire. The resistance 
of the three wires should be 
equal.
Example: For a 4 to 20 mA 
input, a shunt resistor of 
250 Ω ± 0.1% can be used to 
convert to 1-5V input.
A
B
b
Note
RTD input terminals A and B on the dot model are isolated on each channel.  Terminal b is
shorted internally across all channels.  However, for 3 legs isolated RTDs (/N2 option), input b
is also isolated for each channel.
2.3  Input Signal Wiring