VSHP UNIT START-UP SHEET 
INSTALLATION INFORMATION 
Job Name____________________________ 
City______________________Province/State_______________Postal/ZIP Code___________ 
OMEGA Unit Model #____________________________________________________________ 
OMEGA Unit Serial #____________________________________________________________ 
Unit Tag#__________________________ 
Technician___________________________Company_________________________________ 
 
Heating 
Riser Fluid Loop Temperature: 
Entering Water Temperature (EWT):______F 
Leaving Water Temperature (LWT): ______F 
T = EWT - LWT  = _________
o
F             
 
Water Flow Rate (GPM):______ 
(units with optional balancing valve see nameplate for 
GPM rating) 
Air Temperature  (Measure the difference in 
temperature across air coil) for measuring 
sensible capacity: 
T = LAT - EAT 
Sensible Capacity (Btuh) = T x CFM x 1.08 
Entering Air Temperature (EAT):______F 
Leaving Air Temperature (LAT): ______F 
T = _________
o
F         
Sensible Capacity (Btuh) = _________ 
 
Fan Speed Used:  Low  Med  High 
 
Compressor Amp:    ________ 
Fan Amp:      ________ 
Run Time For Test:    ________ 
Cooling 
Riser Fluid Loop Temperature: 
Entering Water Temperature (EWT):______F 
Leaving Water Temperature (LWT): ______F 
T = LWT - EWT  = _________
o
F             
 
Water Flow Rate (GPM):______ 
(units with optional balancing valve see nameplate for 
GPM rating) 
Air Temperature  (Measure the difference in 
temperature across air coil) for measuring 
sensible capacity: 
T = EAT - LAT 
Sensible Capacity (Btuh) = T x CFM x 1.08 
Entering Air Temperature (EAT):______F 
Leaving Air Temperature (LAT): ______F 
T = _________
o
F         
Sensible Capacity (Btuh) = _________ 
 
Fan Speed Used:  Low  Med  High 
 
Compressor Amp:    ________ 
Fan Amp:      ________ 
Run Time For Test:    ________