OMEGA | WATER SOURCE HEAT PUMPS OMEGA-VSHP.F-IOM-1907
13 www.omega-heatpump.com
7. Open up your internet browser (i.e. Explorer, Google
Chrome) and type in the following address
192.168.0.99.
8. The following home page will load for the controller
software. Below is a screen shot of the interface (version
5.4 software is shown).
9. An event log feature called Log Dump allows for re-
cording unit operation information during faults or at start
-up as a troubleshooting aid. For example in the figure
below the first line item indicates Yterminal was ener-
gized (Y=1) when the Cooling (CLG=1) and tripped on
Low Pressure fault (LP=0).
Captured unit controller details include: Y’ ,’O/B’, CPR
=compressor, RV’= reversing valve, HTG = heating,
CLG = cooling, LP = low pressure, HP = high pres-
sure, Fan, Condensate, LPALM = low-pressure alarm,
HPALM = high-pressure alarm.
. The following home page will load for the controller
software. Below is a screen shot of the interface (version
5.4 software is shown).