OMEGA-VSHPe.F-IOM-2205
14
This mode is disabled during the recycled air defrost mode.
ERV FAN SETTINGS
ERV Fan Setting
The ERV fans are factory set to default position. It is recommended to perform an air balance to determine required
fan speeds - Low and High. The potentiometers located on the ERV board controls the Low and High fan speeds.
These speeds are controlled using a PWM signal from 0% to 95% Torque. The range of the potentiometer is 8
oclock to 4 oclock.
High Speed
Potenometer
Speed Switch
Low Speed
Potenometer
Rotate clockwise to
increase fan speed,
rotate counterclock-
wise to reduce fan
speed.
ERV Fan Performance
0.00 0.025 0.05 0.075 0.10 0.15 0.20 0.25 0.30 0.40 0.50
25% Speed @ 6 Watts 10 O'clock 43 34 28 22 18 12 - - - - -
37% Speed @ 13 Watts 11 O'clock 70 54 43 34 27 15 7 - - - -
45% Speed @ 18 Watts
12 O'clock 85 67 55 44 35 23 15 - - - -
57% Speed @ 30 Watts 1 O'clock 111 95 83 74 68 54 45 37 30 21 15
69% Speed @ 43 Watts 2 O'clock 139 124 114 106 104 91 82 73 63 53 44
82% Speed @ 61 Watts 3 O'clock 168 155 150 141 139 127 119 107 96 85 72
95% Speed @ 82 Watts 4 O'clock 187 172 166 157 156 145 137 124 115 105 91
ESP (External Static) inwg
% PWM Signal / Power
Potentiometer
Dial Setting
Notes:
All airflow ratings are taken at lowest voltage rating of dual rating (ie. 208 volt).
ERV external static setting is based on exhaust duct run.
ESP capability shown per fan.
Recommended ERV fan speeds are field set to match duct static. Default factory settings may not match site conditions and
requirements.
Watts includes both ERV fans.
Internal Manual OA Slider Damper may be used to control OA introduction in the event of variable OA conditions (i.e. wind stack
effect)