OMEGA-VSHPe.F-IOM-2205
23
Riser Length Reference Measurements
Notes:
Risers are posioned relave to cabinet using a standard TopDatum reference (oponal BaseDatum). Top Datum
Oset indicates where the top of riser will be located relave to top of cabinet. A Base Datum indicates where boom
of riser will be located relave to base of cabinet.
Upon request Omega will provide 3 inch deep swage on risers of same pipe size (oponal for all risers) for connecon to
units on the oor below.
Risers should insert 2 inches into the 3 inch deep swage connecon (minimum 1 inch inseron is required)
Riser Length = Floor Clearance Height + Slab Thickness + 2 inch (overlap) (Rounded up to 120” or 144”).
Omega supplies two standard riser lengths, 120” (10’) and 144” (12’), to be eld cut on-site.
Omega does not supply extension tailpieces or transion riser pieces for joining dissimilar piping sizes. Items are eld
provided.
Risers available in Type L and Type M/DWV copper.
Condensate riser comes standard with 3/8 inch thick closed cell insulaon to prevent condensaon.
Oponal insulaon on supply and return risers is available.
Cabinet
Height
5"
Floor
Clearance
Height
Slab
Thickness
2"
Overlap with
Connected Pipe
3"
Extended From
Unit Top (Std.)
3"
Swage
End
Slab Thickness
+
Desired Overlap
Slab
Unit Top
(Datum)
Custom vertical
riser offset
positions taken from
above Unit Top
(Optional) Offset
taken from
Unit Bottom
Unit Bottom
(Datum)
Slab
Bottom
Datum
Top
Datum