28
< TTL I/O Unit >
C200H-series Unit
Corresponding CJ-series Unit
Description
Difference
C200H-MD501
CJ1W-MD231
I/O Unit with connector for 16
inputs and 16 outputs.
*The CJ-series Unit does not
support dynamic outputs.
Change the wiring for static
outputs.
*We recommend you to
replace this Unit with
CJ1W-MD563 (32 inputs/32
outputs) for TTL I/O.
1) Connector
2) Output method
(Dynamic or static mode Static mode only)
3) Internal current consumption
(5 VDC: 180 mA 130 mA)
Based on specifications in static output mode
< Output circuit >
4) No. of circuits (8 points/common x 2 circuits
16 points/common x 1 circuit)
5Output circuit specifications
Output voltage range
(5 VDC 12 to 24 VDC)
Residual voltage (0.4 V -> 1.5 V)
ON response time (0.2 ms 0.1 ms)
OFF response time (0.3 ms 0.8 ms)
< Input circuit >
6) No. of circuits (8 points/common x 2 circuits
16 points/common x 1 circuit)
7) Input circuit specifications
Input voltage (5 VDC 24 VDC)
Input impedance (1.1 3.3 kΩ)
ON voltage (3 VDC 14.4 VDC)
OFF voltage (1 VDC 5 VDC)
5 VDC/16 inputs (3.5 mA),
5 VDC/16 outputs (35 mA,
Sinking), Connector
(Special I/O)
24 VDC/16 inputs (7 mA),
12 to 24VDC/16 outputs
(0.5 A, Sinking), Connector