40 Programmable Controllers SYSMAC CS1G/H
● Industrial Switching Hubs
■ Controller Link Units
● Controller Link Options
*1. Use the following special cable for shielded, twisted-pair cable.
• ESVC0.5 × 2C-13262 (Bando Electric Wire: Japanese Company)
• ESNC0.5 × 2C-99-087B (Nihon Electric Wire & Cable Corporation: Japanese Company)
• ESPC 1P × 0.5 mm
2
(Nagaoka Electric Wire Co., Ltd.: Japanese Company)
• Li2Y-FCY2 × 0.56qmm (Kromberg & Schubert, Komtec Department: German Company)
• 1 × 2 × AWG-20PE+Tr.CUSN+PVC (Draka Cables Industrial: Spanish Company)
• #9207 (Belden: US Company)
*2. When using wire-to-optical (H-PCF) cable, use a H-PCF cable (for both Controller Link and SYSMAC LINK) or a H-PCF optical fiber cable with connector.
*3. When using wire-to-optical (GI) cable, use a GI optical cable (for Controller Link).
*4. • Up to four Pre-Ver. 1.2 Controller Link Units (both CS1W-CLK21-V1 Wired Units and CS1W-CLK@2-V1 Optical Units combined) can be mounted to the CS1
CPU Backplane (CS1W-BC@@@) and CS1 Expansion Backplanes (CS1W-BI@@@) of one PLC.
• Up to eight Controller Link Units with unit version 1.2 or later (both CS1W-CLK21-V1 Wired Units and CS1W-CLK@2-V1 Optical Units combined) can be
mounted to the CS1 CPU Backplane (CS1W-BC@@@) and CS1 Expansion Backplanes (CS1W-BI@@@) of one PLC.
*5. The CD-ROM contains the following software.
• Controller Link (PCI) Driver
• FinsGateway Version 2003 (PCI-CLK Edition)
• FinsGateway Version 3 (PCI-CLK Edition)
• Setup Diagnostic Utility
• C Library
Product name
Appearance
Specifications
Accessories
Current
Consumption
(A)
Model
Standards
Functions
No. of
pors
Failure
detection
Industrial
Switching Hubs
Quality of Service (QoS):
EtherNet/IP control data priority
Failure detection:
Broadcast storm and LSI error detection
10/100BASE-TX, Auto-Negotiation
3
No
• Power supply
connector
0.22 W4S1-03B
UC, CE
5
No 0.22 W4S1-05B
5
Ye s
• Power supply
connector
• Connector for
informing error
0.22 W4S1-05C CE
Unit
type
Product name Specifications
Mountable Racks
No. of
unit
numbers
allocated
Current
consumption
(A)
Model Standards
CPU Rack
C200HX/
HG/HE
Expansion
I/O Rack
CS1
Expansion
Rack
CS1 Long-
distance
Expansion
Rack
SYSMAC
BUS
Slave
Rack
CS1W-BC CS1W-BI
5 V
system
26 V
system
@@3 @@2 @@3 @@2
CS1
CPU
Bus
Unit
Controller Link
Unit
Wired shielded
twisted-pair cable *1
*4
Ye s
*4
Ye s N o
*4
Ye s
*4
Ye s Ye s N o
1 unit
number’s
words
0.33 --- CS1W-CLK23
UC1, N, L,
CE
Optical ring H-PCF
cable *2
*4
Ye s
*4
Ye s N o
*4
Ye s
*4
Yes Yes No 0.52 --- CS1W-CLK13
Optical ring GI
cable *3
*4
Ye s
*4
Ye s N o
*4
Ye s
*4
Yes Yes No 0.65 --- CS1W-CLK53
Controller
Link Support
Board
Wired shielded twisted-pair
cable *1
• CD-ROM × 1 *5
• Installation Guide (W467) × 1
• Communications Connector × 1
---
3G8F7-CLK23-E
CE
H-PCF optical model • CD-ROM × 1 *5
• Installation Guide (W467) × 1
• Optical Fiber Cable Bracket × 1
• Power Supply Connector × 1
3G8F7-CLK13-E
GI optical model 3G8F7-CLK53-E
Product name Specifications Model Standards
Relay Terminal Block for
Wired Controller Link Unit
Use for Wired Controller Link Units (set of 5).
These products are not mounted to the
PLC. (They are installed individually on
DIN Rail or with screws.)
CJ1W-TB101
---
Controller Link Repeater
Unit
Wire-to-Wire Model CS1W-RPT01
UC1, CE
Wire-to-Optical (H-PCF) Model *2 CS1W-RPT02
Wire-to-Optical (GI) Model *3 CS1W-RPT03
CS1W-RPT01
PWR
T/R1
T/R2
SL1
TER SW
TER SW
ON
SL2
DC24V
INPUT
1 BAUD
2 RATE
SW1