Dual Output 3-Way Signal Isolator K3FP-VS-UI-2I 13
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Precautions
Refer to pages 38 and 39 for common precautions.
Precautions for Correct Use
Diagnostics Indicator
The diagnostics indicator (LED) inside the translucent cover lights
when the input or output signal exceed the set range while the limit
function is enabled (i.e., pin 4 on DIP switch S1 turned ON).
The diagnostics indicator flashes to indicate parameter memory
errors. If this occurs, the Unit must be inspected at the factory.
93.1 6.2
102.5
K3FP-VS-UI-2I
Note: 1. Use solid wire with a diameter
of 2.5 mm
2
max. or bar
terminals with insulation
sleeves for terminal
connections.
To preserve dielectric strength
after connection, the length of
the exposed conductive part
inserted into the terminal must
be 12 mm max.
2. Screw Tightening Torque
Recommended torque:
0.5 N·m
12 mm max. 12 mm max.
For 2.5-mm
2
(max.)
solid wire:
For bar terminals with
insulation sleeves: