24 RTD Transducer K3FP-RS-UI
■ Input Specifications
Note: Set the start and end temperatures using the DIP switch to
50
°C or higher.
■ Output Specifications
Nomenclature
Connecting
cable
Solid
wire
0.14 to 2.5 mm
2
Stranded
wire
0.2 to 2.5 mm
2
AWG 24 to 12
Wire
stripping
length
12 mm
Degree of protection IP20
Housing material PBT
Weight 54 g
Safety standards UL 508
EMC EMI:
Radiated EMI: EN 55011
EMS:
ESD immunity: EN 61000-4-2
Rated electromagnetic field immunity:
EN 61000-4-3
Burst immunity: EN 61000-4-4
Surge immunity: EN 61000-4-5
Conducted disturbance immunity:
EN 61000-4-6
Input signal
Item
PT100 platinum resistance thermometer
(conforms to IEC 60751)
Measurement range
−150 to 850°C
Min. measurement
span
Min. 50
°C
Max. input signal 30 V
Connection method 2-conductor, 3-conductor, or 4-conductor
Sensor input current 1 mA
Max. permissible
conductor
resistance
10
Ω per conductor
Output signal
Item
0 to 20 mA DC,
4 to 20 mA DC,
20 to 0 mA DC,
20 to 4 mA DC
0 to 5 V DC,
1 to 5 V DC,
0 to 10 V DC,
10 to 0 V DC
Allowable load
impedance
500
Ω max. (20 mA) 10 kΩ min.
Max. output
signal
23 mA 12.5 V
Non-load
voltage
12.5 V max. ---
Short-circuit
current
--- 10 mA max.
Ripple 20 mVpp max. (500
Ω) 20 mVpp max.
Operation
during sensor
faults
0% to 105%
Diagnostics indicator (red)
DIP switch S3
1
2
3
4 Inputs: PT100 Platinum Resistance Thermometer Sensor
7
8 Supply voltage
5
6 Output signals
Translucent cover
Snap for mounting DIN rail
DIN rail bus connection
DIP switch S2
DIP switch S1