RTD Transducer K3FP-RS-UI 27
Output Status for Errors
Relationship between Output Signal Range Selection and Output Status for Errors
Output Signal Ranges 0 to 20 mA or 20 to 0 mA
Output Signal Ranges 4 to 20 mA or 20 to 4 mA
Output Signal Ranges 0 to 10 V or 10 to 0 V
Output Signal Range 0 to 5 V
SWITCH DIP switch S2
ON
OFF
78
Output status
for errors
When disconnected on
platinum resistance
thermometer side
Above measurement
range
Below measurement
range
When short-circuited on
platinum resistance
thermometer side
A ❍❍Held at 5% of maximum
rated output.
Held at 2.5% of maximum
rated output.
Held at minimum rated
output.
Held at minimum rated
output.
B ●❍Held at 5% of maximum
rated output.
Held at 2.5% of maximum
rated output.
Held at
12.5% of
minimum rated output.
Held at 25% of minimum
rated output.
C ❍●Held at 5% of maximum
rated output.
Held at maximum rated
output.
Held at minimum rated
output.
Held at 5% of maximum
rated output.
D ●●Held at minimum rated
output.
Held at maximum rated
output.
Held at minimum rated
output.
Held at minimum rated
output.
Output status
for errors
DIP switch S2 When disconnected on
platinum resistance
thermometer side
Above measurement
range
Below measurement
range
When short-circuited on
platinum resistance
thermometer side
7 8
A ❍❍21 mA 20.5 mA 0 mA 0 mA
B ●❍21 mA 20.5 mA 0 mA 0 mA
C ❍●21 mA 20 mA 0 mA 21 mA
D ●●0 mA 20 mA 0 mA 0 mA
Output status
for errors
DIP switch S2 When disconnected on
platinum resistance
thermometer side
Above measurement
range
Below measurement
range
When short-circuited on
platinum resistance
thermometer side
7 8
A ❍❍21 mA 20.5 mA 4 mA 4 mA
B ●❍21 mA 20.5 mA 3.5 mA 3mA
C ❍●21 mA 20 mA 4 mA 21 mA
D ●●4 mA 20 mA 4 mA 4 mA
Output status
for errors
DIP switch S2 When disconnected on
platinum resistance
thermometer side
Above measurement
range
Below measurement
range
When short-circuited on
platinum resistance
thermometer side
7 8
A ❍❍10.5 V 10.25 V 0 V 0 V
B ●❍10.5 V 10.25 V 0 V 0 V
C ❍●10.5 V 10 V 0 V 10.5 V
D ●●0 V 10 V 0 V 0 V
Output status
for errors
DIP switch S2 When disconnected on
platinum resistance
thermometer side
Above measurement
range
Below measurement
range
When short-circuited on
platinum resistance
thermometer side
7 8
A ❍❍5.25 V 5.125 V 0 V 0 V
B ●❍5.25 V 5.125 V 0 V 0 V
C ❍●5.25 V 5 V 0 V 5.25 V
D ●●0 V5 V0 V0 V