34 Limit Value Switch K3FP-SL-UI
■ Input Specifications
■ Output Specifications
Nomenclature
Safety standards UL 508
EMC EMI:
Radiated EMI: EN 55011
EMS:
ESD immunity: EN 61000-4-2
Rated electromagnetic field immunity:
EN 61000-4-3
Burst immunity: EN 61000-4-4
Surge immunity: EN 61000-4-5
Conducted disturbance immunity:
EN 61000-4-6
Input signal
Item
0 to 20 mA DC 0 to 10 V DC
Input impedance Approx. 50
Ω Approx. 110 kΩ
Max. input signal 100 mA 30 V
Alarm output setting Using 25-speed potentiometer
Output signal
Item
SPDT
Contact output
status display
Yellow indicator (LED)
Applicable load 250 V AC, 2 A
Contact material AgSnO
2
Max. contact voltage 250 V AC
Max. contact current 2 A
Max. switching
capacity
500 VA (250 V AC)
Mechanical life 20 million operations
Electrical life 200,000 operations
Hysteresis 0.1%, 1% 2.5%, 5% (can be set using the
DIP switch)
Contact drive
method
NO, NC (can be set using the DIP switch)
Contact operation
(delay time)
0 s, 1 s, 2 s, 3 s, 4 s, 6 s, 8 s, 10 s
(can be set using the DIP switch)
1 Not connected
7
8 Supply voltage
5
6 Input signals
Translucent cover
Snap for mounting DIN rail
DIN rail bus connection
Potentiometer for adjustment
Error indicator (red)
DIP switch S1
2
3
4 Output: SPDT
Status indicator (yellow)