4 3-Way Signal Isolator K3FP-YV-I-I/K3FP-YV-U-U
Input Specifications
Output Specifications
Nomenclature
Ambient storage
humidity
95% max. (with no condensation)
Connection method Screw connections (M3)
Tightening torque 0.5 N·m
Connecting
cable
Solid
wire
0.14 to 2.5 mm
2
Stranded
wire
0.2 to 2.5 mm
2
AWG 24 to 12
Wire
stripping
length
12 mm
Degree of protection IP20
Housing material PBT
Weight 55 g
Safety standards UL 508
EMC EMI:
Radiated EMI: EN 55011
EMS:
ESD immunity: EN 61000-4-2
Rated electromagnetic field immunity:
EN 61000-4-3
Burst immunity: EN 61000-4-4
Surge immunity: EN 61000-4-5
Conducted disturbance immunity:
EN 61000-4-6
Item Model K3FP-YV-I-I K3FP-YV-U-U
Input signal
Item
0 (4) to 20 mA DC 10 (0) to 10 V DC
Input impedance Approx. 50
Approx. 100 k
Max. input signal 50 mA 30 V
Output signal
Item
0 (4) to 20 mA DC
10 (0) to 10 V DC
Allowable load
impedance
500
max. 10 k min.
Max. output signal 28 mA 12.5 V
Non-load voltage 12.5 V max. ---
Short-circuit
current
--- 22 mA max.
Ripple 20 mV pp max. (500
) 20 mV pp max.
Span adjustment
range
±0.5%
1
2 Input signals
3
4 Supply voltage
7
8 Supply voltage
5
6 Output signals
Translucent cover
Snap for mounting DIN rail
DIN rail bus connection
Potentiometer for adjustment
Note: The potentiometer is for adjustment at the factory. Do not adjust the potentiometer.