I
1.
The slide tap on adjustable resistor
R21,
located in
the generator air outlet,
should
be set .to give
about 2 amperes charging rate. For applications
requiring frequent starts, check battery charge
condition (specific gravity) periodically and if
necessary, increase charging rate slightly (slide
tap nearer ungrounded lead) until
it
keeps battery
charged. Having engine stopped when read-
justing avoids accidental shorts. Avoid
overcharging.
2.
If
charge winding
AC
output
is below
19
volts on
12
volt battery charge models, test the charging
circuit
for
opens
or
grounds
in the leads and
charging winding.
If
leads are defective, replace
them.
If
winding is defective, replace generator
stator.
..
3.
I f a separate automatic demand control is used
for
starting and stopping, adjust charge rate
for·
maximum.
4.5 . amperes. This normally keeps
battery charged even
if
starts
occur
as often
as
15
minutes apart. .
BATTERY CONNECTIONS
The
battery is connected
for
negative (-) ground,
Figu
re
11
. Be
su
re
all battery connections are secu
reo
BatterY polarity must agree with the rectifier located
in the control box. If battery
ground
must be changed,
reverse the rectifier connection in the control box.
K""
STARTING
MOTOR
STARTER
~~"""""".,;;...-
CRANKED
SETS
-
BATTERY
POSITIVE
12.
V.BATTERY
+
...
I
-
~
I~
~
CABLE
SIZE
2
0
00
000
0000
4
ft.
S .ft.
7
ft.
9 ft,
II
ft~
14·ft.
FIGURE
11.
BATTERY
CONNECTIONS
~
If
battery·
polarity
is reversed, damage
will
L.-..';.~
occur
within
3
minutes
while stopped
or
5
seconds
while
running. Alternator
windings
will
be
damaged
almost instantly
if
battery charging
circuit
Is shorted between
resistor
R21
and the
B1
end
of
the charging winding.
See Specifications
for
minimum
12
volt battery re-
quirements. Connect battery positive (+) to starter
engaging solenoid terminal post, Figure 11. Connect
battery negative
(-)
to a good
ground
on the engine.
WIRE
SIZE
DISTANCE
#18
to
125 ft. (39 m)
#16
to.
200 ft. (62 m)
#14
to
300 ft. (93 m)
#12
to 500 ft.
(155m)
FIGURE
12.
REMOTE
SWITCH
CONNECTIONS
REMOTE ST ART
-s..TOPSWITCH
(OP-
TIONAL) .
For remote control
sfartingand
stopping, use 3.,wires
to connect the remote switch (single pole, double
throw, momentary contact,
center-off
type)
to
the
terminal block marked
Bot,
1,
2,
3,in
the
set
control
box
using
vvire
sizes
as
listed in Figu
re
12.