TM5-6115-585-34
-
-
-
-
I
!
1
!
NAVFAC
P
-
8-623-34
TO
-
35C2-3-455-2
TM
-
05684C
/
05685B
-
34
CHAPTER
6
MAINTENANCE
OF
CONTROL
SYSTEM
Section
I.
DESCRIPTION
AND
FUNCTION
6-1
.
DC
CONTROL
SYSTEM
.
6-3
.
VOLTAGE
REGULATOR
.
Refer
to
the
Operator
and
Organizational
Maintenance
Manual
for
the
description
and
function
of
the dc
control
system
.
Excitation
current
is
controlled
through
the
static
type
automatic
voltage
regulator
.
The
voltage
regu
lator
continuously
compares
the
output
voltage
of
the
synchronous
generator
with
a
stable
reference
volt
age
.
The
difference
between
the
two
voltages
con
stitutes
an
error
signal
which
indicates
an
output
voltage
that
is
higher
or
lower
than
the
generator
set
point
.
This
error
signal
is
amplified
and
used
to
control
the
direct
current
output
of
the
voltage
regu
lator
which
is
applied
to
the
control
windings
of
the
current
-
voltage
transformers
.
6-2
.
AC
INSTRUMENTATION
SYSTEM
.
Refer
to
the
Operator
and
Organizational
Maintenance
Manual
for
description
and
function
of
the
ac
instrumentation
system
.
Section
II
.
MAINTENANCE
6-4
.
CONTROL
CUBICLE
.
a
.
Wiring
Harness
.
(
3 )
Percent
Current
Meter
(
M4
) (
17
,
figure
6-3
)
.
Connect
an
ac
test
ammeter
in
series
with
the
%
rated
current
meter
.
Operate
Generator
Set
with
a
single
phase
load
.
Continue
adding
load
to
set
until
meter
reads
0.75
amps
.
Meter
(
M4
)
should
read
100
%
+
2
% .
Replace
meter
if
necessary
.
(
1
)
Remove
.
Disconnect
wires
of
wiring
harness
from
all
components
.
Remove
clamp
attaching
harness
to
control
panel
and
remove
harness
.
(
2
)
Repair
.
Table
6-1
lists
the
wire
number
,
gauge
,
color
,
length
and
terminal
lugs
for
each
wire
in
the
harness
.
Repair
consists
of
replacing
wires
as
required
.
(
4 )
AC
Voltmeter
(
M5
) (
18
,
figure
6-3
)
.
Attach
test
ac
voltmeter
in
parallel
(
across
terminals
)
with
panel
ac
voltmeter
(
M5
).
Operate Generator
Set
and
compare
readings
of the
two
meters
.
Panel
voltmeter
must
be
accurate
to
$
2.5
%
,
except
between
115
and
125
volts
,
accuracy
must
be
£
3
volts
and
between
200
and
250
volts
,
accuracy
must
be
+
5
volts
.
If
panel
meter
does
not
meet
these
requirements
,
replace
meter
.
(
3)
Installation
.
Install
harness
by
connecting
wires
to
components
per
figure
6-1
.
Attach
harness
to
control
panel
with
clamp
.
c
.
Meters
(
remove
).
b
.
Meters
(
on
equipment
test
).
(
1
)
Frequency
Meter
(
M3
) (
16
,
figure
6-3
) .
Tag
and
disconnect
two
leads
from
meter
.
Remove
three
screws
,
lockwashers
,
and
nuts
attaching
meter
to
panel
and
remove
meter
.
(
1
)
Frequency
Meter
(
M3
)
(
16
,
figure
6-3
)
.
Con
nect
a
frequency
meter
of
known
accuracy
to
single
phase
output
terminals
of
load
terminal
board
.
Make
certain
reconnection
switch
is
in
proper
position
for
single
phase
output
.
Operate
Generator
Set
and
check
readings
of
panel
meter
(
M3
)
against
test
frequency
meter
.
If
panel
meter
does
not
give
the
same
reading
as
the
test
meter
,
test
transducer
as
given
in
(
2
)
below
.
(
2
)
Frequency
Transducer
(
A3
) (
56
,
figure
6-3
)
.
Test
transducer
using
the
same
procedure
as
for
testing
frequency
meter
.
If
transducer
does
not
give
oper
meter
reading
,
replace
the
transducer
and
/
or
the
meter
.
( 2 )
Frequency
Transducer
(
A3
)
(
56
,
figure
6-3
)
.
Tag
and
disconnect
four
leads
to
frequency
transducer
.
Remove
four
screws
(
54
)
and
nuts
(
55
)
attaching
transducer
to
back
of
control cubicle
and
remove
transducer
.
( 3 )
Percent Current
Meter
(
M4
)
(
17
,
figure
6-3
)
.
Tag
and
disconnect
two
leads
from
meter
.
Remove
three
screws
,
lockwashers
,
and
nuts
attaching
meter
to
control
panel
and
remove
meter
.
Change
4
6-1