DATA MULTI ANUAL
691-010
Dimensions
I
O
II
O
~
r
O
60
Manual User
DIGITAL TIME SWITCH
Read aU the instnu:tions carefully
00000000
1 2 3 • 5 6 7 8
[jl][!l:JDrllIIl!l!I
IiiliIODl!l!ItmI
Ei
9
W
II U U
U ~
16
00000000
• DATAMULTIANUAL
is a digital time switch with 4 independent and not live command
circuits, designed for the control of every kind of electricai installation. It allows a daily, weekly,
monthly and yearly planning or in a prefixed time (day, month, year).
Pulse Program: from 1 to 59 seconds, Random Program, Automatic switch to summer/winter
time, holiday program and hour counter
II
SAFETY WARNINGS
Toguarantee the safety levels bulit into the device, proceed as follows:
1) The appliance has to be installed by a specialist operator
2) The appliance has to be installed In such a way that the terminals are inaccessible after
installatlon
3) Wheninstalling the appliance, follow the wiring diagrams carefully
4) Betore touching the terminaIs, make sure the connectars to be altached to the appliance
are not live
5) Do not power
or
connect the instrument if any part of it is damaged.
TECHNICAL SPECIFICATIONS
Wiring diagrams
Power supply: 230 VAC (-15%/+10%)
24 VACIDC (-15%/+10%)
50/60 Hz
16(1O)A 250V-
16(10) A/250 V -
16(10) A/250 V-
Frequency:
Switching power:
Contact capacity:
incandescent lights max
Fluorescent lights max
Type action:
• Absorption:
1500 W per channel
600 W per channel
IB, IS, IT and lU
max 22VA at 230V 50Hz
max 3W at 230V 50Hz
4 mono-stable relays (channels) in exchange
in forrnat VYYY.MM.DD
(calendar from 01.01.1999 to 31.12.2172)
±ls per day (lOppm)
with 5 year charge reserve 20 "C
max 100 (ON + OFF + impulse)
1 minute
OoC.,. +50
-c
lP20 (IP41 after installation)
II aceording to EN 60335 in conditions of correct assembly
normal pollution
Outputs:
• Annual clock
Clock precision
Lithium battery
Number of programrnes:
Programming resolution:
Operating temperature:
Protection level
Insulation class:
User conditions:
INSTRUMENT RESET
Device description
For the
PARTIALRESET
of the instrument, press the
"R"
key.
In this way, the date is set to the default value 2001.01.01 and the RANDOM is set to OFF if
active.
The clock is zeroed and the display will show a flashing 00:00.
For the
TOTALRESET
of the instrument, press key
"R"
followed by "PRG" three seconds
later. In this way, in addition to the partial reset operations, ali the prograrnmes are cancelled
and the timer is zeroed.
In the centre of the display, the
CLEAR
message will appear followed by a flashing 00:00.
DATA CONFIRM AND
PROGRAMMING FORWARD
QOCKSElTING AND RAPID EX'Tl~m~~iü;;;=l
FROM PROGRAMMING
Note: after installation, carry aut the total reset of the instmment before any other
operation.
PROGRAMMING
,,=c---!t_MANUAL RELAY COMMAND
"CH1...CH4"
SETTING THE TIME AND DATE
RESET-p;====f •...•Ei'="-l'F'==="l
INCREASElMODIFY/SELEaION
OF A PARAMETER
DECREASElMODIFY/OESELEaION
OF A PARAMETER
DAYS
OFTHEWEEK
PROGRAMM ING
STATUS SYMBOLS
HOUDAY
PROGRAMME SYMBOL
To set the time and date, press the"
c9 "
key.
The hour and minutes will be displayed, and the seconds will start to flash. Press the
"Ji.'+"
key to synchronise these to the next minute or the "T'-" key to synchronise them to the
previous minute.
Press
"OK"
to go to the regulation of the minutes (the seconds will disappear and the date
will be displayed),
Press the
"Ji.'+"
or "T'-" keys to increase/decrease the minutes ..
Press
"OK"
to go to the regulation of the hours, year, month and day (set with the keys
"J!i./+"
and
"'ffl-").
If "OK"
is pressed after the day is set, the system returns to the setting of the seconds.
If the"
C9"
key is pressed at any time, the system returns to the normal display rnode, with
the exception of the modifications made.
If no key is pressed for at least 30 seconds, the system automaticaily returns to normal
display mode, with the exception of the rnodifications made.
PROGRAMMING
SUMMERTIME
SYMBOL
IMPULSE
PROGRAMME
SYMBOL
The programming function can be used to set the times for the ON, OFF and impulse
operation" O " events.
Up to 100 events can be prograrnmed in the 4 channels.
To enter programming mode, press
"PRG".
The
"PRG"
message appears and the channel indication
"CHI"
will flash. Select the channel
required with the
"CHI" ... "CH4"
keys and press
"OK".
The instrument will now display the mcssage
"PROG",
the date and time fields (empty) and
the
ON
and
OFF
syrnbols for the channel and"
O
"will flash.
If events are already programmed for the channel selected, the first of these will appear.
Press
"OK"
to display ali the progranimes already memorised for the channel in sequence,
followed by the screen display for a new programming operation.
Note: if the maximum number of programmes that can be set has been reached, the
"FULL"
message
will appear.
Press
"OK"
agairi to leave programming mode and see the number of programrnes still
available for the channel in question .
To select the type of event to be set (ON, OFF or IMPULSE) use keys
"Ji.'+"
and "T'-" until
the event required begins to flash, and confirm with
"OK"
YEARlMONTH/DAY"
INDICATION
WINTERTIME
..J,z=====I=====t======::::J
SYMBOL
RANDOM
PROGRAMME SYMBOL
HOURS/MINUTES
INDICATlON
•
ORBIS TECNOLOGíA ELÉCTRICA, S.A.
Lérida, 61 E-28020 MADRID
Teléfono:+ 34 91 5672277; Fax:+34 91 5714006
E-mail: info@orbis.es
http://www.orbis.es