Seng of the chamber pressure value is done in the control box. During start -up the elevator belt runs at
fast speed. When chamber full level (pre set value) is achieved, the speed on elevator is reduced to obtain a
higher density on the bale. When the value of chamber pressure is reached, the bale is ready for lm or net
binding.
Parameters to be set in control box is:
Fully pressed bale: 100 - 240bar
Start slow speed, elevator belt: 0 - 100% by pre set pressure
Material: Wood chips
Chamber pressure: 200bar
Chamber full -level: 80%
When the sensor register a chamber pressure of 160bar (80% of 200bar), the elevator belt speed is reduced
to “slow speed”. The belt speed will remain slow unl chamber pressure reaches 200 bar.
Chamber sensor, oil-pressure, right side cabinet