1. Check heating output
heck the controller’s dis
lay
wh
has com
letely o
ened the
1.1 If it is not com
letely o
en,
you can turn up t
e
eat,
o to sect
on 2.
1.2 If it is completely open (as in the
ia
ram), check the followin
:
If it is too cold with freezing out-
door temperatures
Turn the control knob so that the top 1.
edge of the display reads “L1 Curve”
Press “OK”2.
Press “OK”, change the “-20” setting so 3.
it is bigger, e.g., 4 °C, press “OK”
At the same time change the “0” set-4.
ting so it is a little bigger, e.g., 4 °C
Exit and press “ESC” to con rm the 5.
changes
2. Adjust settings
Finely adjust basic heating
If the room temperature is too low no
matter what the outdoor temperature,
adjust control using the ne adjustment
as follows:
Make sure that the top row of the 1.
display reads “If it is too warm or too
cold, press OK” ( If necessary, press
the ESC button a number of times)
Press “OK”2.
Turn the control knob to change 3.
the temperature and press “OK” to
con rm
OUMAN EH-800 Heating controller
Quick Guide: T
oo cold
Note! Wait long enough for the
setting changes to have time to ef-
fect the room temperature. A long
enough waiting time is 24 hours.
OK
The picture displays default settings for normal
radiator heating,
!
If there were faults, get them xed.
Adjust settings after that.
If nothing has to be xed and the
control valve is completely open, ask
a professional to nd out where the
fault is.
Is the temperature in the boiler or •
accumulator high enough.
Is the circulating pump turning•
Is the pressure in the heating net-•
work high enough.
Make sure that the temperature •
measurements are correct. If the
temperature sensor is damaged,
contact Ouman Oy maintenance
Make sure that the control valve is •
not stuck (user manual p. 4).
L1 Heating curve
-20 = 58 °C
0 = 41 °C
+20 = 18 °C
Min. limit: 10 Max. limit: 75
+20 -200
°C
20
40
60
80
Heating fi ne adjust: turn control knob
Room temperature change +1.5 °C
-
+
Info: Effect on supply water temp. 6.0 °C
Confi rm: press OK, Cancel: press ESC