2-7. Link Controller Address Locations
2/99 2-31 U3-1021
Westinghouse Proprietary Class 2C
2-7. Link Controller Address Locations
An Ovation I/O module has 16 address locations, but typically does not use all 16
addresses.
There are four possible address locations in each I/O module that are reserved for
special use. Three of these addresses provide configuration (Write) and status
(Read) information:
Address word 13 (D in Hex) is present for every module and is used for
configuration and status (see
Table 2-8). The module status provides diagnostic
information that is read by the Controller when it is on-line. The status register
can be read by using the Point Information window at an Ovation Operator
Station (see the Bit Pattern Field on the Hardware Tab).
Address word 14 (E in Hex) is used as a secondary or expansion configuration
register and is only used when needed.
Address word 12 (C in Hex) is used for reporting point specific fault
information and optionally as an expansion configuration register.
Address word 15 (F in Hex), is used for the module Electronic ID information.
This location and its use is identical for all modules. Refer to
“Ovation I/O
Reference Manual” (R3-1150) for information about the Electronic ID.
Table 2-8 lists the configuration information for the Link Controller module.
Table 2-8. Link Controller Configuration Register (Address 13 or D in Hex)
Bit Configuration Register (Write) Status Register (Read)
0 Configure Module
(1 = configure; 0 = unconfigure, causing an
attention status)
Configured Module
(1 = configured; 0 = unconfigured, causing an
attention status)
1 Force Error
(1 = force an attention status to be read by
Controller; 0 = no forced error)
Forced Error
(1 = forced error to be read by Controller; 0 = no
forced error)
2 Not defined Applications time-out/
3 Not defined Not defined
4 Not defined Not defined
5 Not defined Not defined
6 Not defined Internal Error
7 Not defined External Error
8 Not defined Not defined
9 Reserved Reserved
10 Not defined Not defined
11 Not defined Not defined

Related product manuals