R-Tronic with mote 320 Malfunctions
33
115068283#EN-V01.05.2020
MOTOR BLOCKED Stem (motor operated) of the mote
320actuatorblocked.
MOTOR DEFECT Drive motor defective.
POWERSUPPLYDEFECT Temporary poor power supply.
TIME PROFILE INVALID Incorrect programming of individual
timeprole.
RADIO DISTURBANCE Radio communication disturbed.
ENOCEAN ERROR Possible error at installed wireless
module.
H-SENSOR DEFECT Humidity sensor in the R-Tronic RTF
B/RTFCKdefective.
CO2 SENSOR DEFECT CO2 sensor in the R-Tronic RTFC K
defective.
HIGHPPM CO2 value higher than 2,000 PPM.
KEYDEFECTIVE Button at the R-Tronic does not trig-
ger a function (contact problem).
10.3 Colour codes of the info LEDs at the mote 320 wireless actuator
The following colour codes are shown on the mote 320 wireless actuator.
3x green (slow) Teachin/teachoutprocessor
calibration run successful
3x red (slow) Teachin/teachoutprocessor
calibration run not successful
1x red (every 50 seconds) Error message (e.g. batteries
empty)
1x green (short) Teachin/calibrationbuttonpressed
for at least 2 seconds
5x green (fast) Stem retracted successfully (for
removal)
2x red and green alternately Factory settings restored success-
fully