AFX SERIES® OPERATION MANUAL
SECTION 8: REMOTE PROGRAMMING
Entire Contents Copyright
2016 by Pacific Power Source, Inc. (PPS) All Rights Reserved • No reproduction without written authorization from PPS.
AFX Series Power Source Operation Manual Page 143 of 274
Query Format
MEASure:CURRent:AC#?"
Description
Returns the measured RMS voltage for the selected phase #. If no
phase number is specified, returns the reading for the last selected
phase. This command is equivalent to “MEASure:CURRent[:ACDC]#?”
and is provided for backward compatibility with the UPC controllers.
Returned Data Format
<nr2>
Query Example
MEAS:CURR:AC1?
21.1587
8.4.4 Power Measurement Commands
Query Format
MEASure:POWer#?
Description
Returns the true power for the selected phase # in kW. If no phase
number is specified, returns the reading for the last selected phase.
Returned Data Format
<nr2>
Query Example
MEAS:POWer1?
4.4203
Query Format
MEASure:KVA#?
Description
Returns the true apparent for the selected phase # in kVA. If no phase
number is specified, returns the reading for the last selected phase.
Returned Data Format
<nr2>
Query Example
MEAS:KVA1?
4.8665
Query Format
MEASure:PF#?
Description
Returns the true apparent for the selected phase # in kVA. If no phase
number is specified, returns the reading for the last selected phase.
Returned Data Format
<nr2>
Query Example
MEAS:PF1?
0.9083
8.4.5 Other Measurement Commands
Query Format
MEASure:TEMPerature:AMBient?
Description
Returns the ambient temperature of the power source in degrees
celcius.
Returned Data Format
<nr1>
Query Example
MEAS:TEMP:AMB?
24