EasyManua.ls Logo

PACSystems RX3i - Release History

PACSystems RX3i
18 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8 RX3i PROFINET Controller
GFK-2573U IC695PNC001-BBBB
Release History
Version
Firmware
Revision
Date
Comments
IC695PNC001-
BBBB
3.10
Nov
2018
Hardware change: slight housing dimension change to address issue of
difficulty installing module into a slot with another module already installed in
the left adjacent slot.
IC695PNC001
-BABB
3.10
Oct
2018
Corrects these issues: PROFINET IO Not Scanned After Loss of Both Critical Ring
Ports, Addition of IO Module Causes IO Device to Disconnect, and Bumpless IO Using
Link Change Detection May Fail Using a PNC001-Bxxx as a MRM. Also includes
updates to enhance cyber security.
IC695PNC001
-BABA
3.00
Feb
2018
Redesign hardware and firmware for component obsolescence, reduce power
requirements, and comply with EU RoHS.
IC695PNC001
-AN
2.27
May
2017
Adds support for the Genius Communication Gateway’s (GCG001) Switch BSM and
Enable/Disable Outputs COMMREQs.
IC695PNC001
-AM
2.26
Jun
2016
Supports the Remote Get HART Device Information COMMREQ. Information from a
HART device connected to an RX3i Analog Module in an IC695PNS001 RX3i
PROFINET Scanner may be read into the user application using the Remote Get
HART Device Information COMMREQ.
IC695PNC001
-AL
2.25
Nov
2015
Supports extended PROFINET device Subslot Numbers in order to support additional
3rd party devices. The maximum Subslot Number has been increased from 255 to
21845.
IC695PNC001
-AK
2.20
May
2015
Added support for HART
®
Pass Through feature set over PROFINET . A HART
capable PROFINET scanner (IC695PNS001 or IC695CEP001) must also be employed
to support the HART capable RX3i analog modules over PROFINET. The CPU used in
the application must also contain firmware which supports HART Pass Through.
IC695PNC001
-AJ
2.11
Feb
2015
Increased number of PROFINET Devices that PNC001 can control from 64 to 128.
Still limited to 63 devices in an MRP Ring if the PNC001 is the MRP Ring Manager.
Added new
SFP OK
status bits to existing PNC001 status dword.
Introduced new
Critical Network Port
diagnostic fault configuration and logging.
Configuring ports as critical also forces Copper ports to 100 Mbps.
IC695PNC001
-AH
2.05
Jun
2014
Adds support for COMMREQs required by the Genius Communication Gateway
(GCG001) module.
IC695PNC001
-AG
2.00
Dec
2013
Adds remote PROFINET IO to PACSystems RX3i Hot Standby Redundancy systems.
Also adds MRP status bits.
For details, see
New Features and Enhancements
below.
IC695PNC001
-AF
1.23
Aug
2013
Corrects issue storing PROFINET device configuration greater than 64K bytes in size.
For details, see
RX3i PROFINET Controller IPI,
GFK-2573F.
IC695PNC001
-AE
1.22
Jul
2013
Corrects an issue where, in some configurations, the PNC001 entered a mode that
caused it to repeatedly power up.
IC695PNC001
-AD
1.21
Jul
2012
Addresses a power-up issue affecting the following revisions IC695PNC001-AB and
IC695PNC001-AC.
Although no units that exhibited this issue were shipped, it is recommended to update
firmware to prevent the possibility of encountering a power up issue in the field.
IC695PNC001
-AC
1.20
Mar
2012
Adds support for up to 255 PROFINET IO Devices per RX3i CPU.
®
HART
®
is a registered trademark of the HART Communication Foundation of Austin, Texas USA. Any use of the term HART hereafter
in this document, or any document referenced by this document, implies the registered trademark.

Other manuals for PACSystems RX3i