11
MidiHeat EHA
MA45-32E
ENGLISH
Figure5
3~ 220–240V
Output FusesF1-4 min. cable area
2x9=18kW 32A 6mm
2
2x12=24kW 50A 10mm
2
2x15=30kW 50A 10mm
2
3x12=36kW 50A 10mm
2
3x15=45kW 50A 10mm
2
4x15=60kW 50A 10mm
2
White Pink
Blue Blue
White Pink
Heatingelementconnectedfor220-240V3-phase
3~ 380–415V
Output FusesF1-4 min. cable area
2x9=18kW 20A 2,5mm
2
2x12=24kW 25A 4 mm
2
2x15=30kW 32A 6mm
2
3x12=36kW 25A 4 mm
2
3x15=45kW 32A 6mm
2
4x15=60kW 32A 6mm
2
4x18=72kW 32A 6mm
2
White Pink
Blue Blue
White Pink
Heatingelementconnectedfor380-415V3-phase
Figure4
Figure3
NOTE!
Reconnection from 400V to 230V
Ondelivery,theheaterismarkedwithanameplateandconnectedfor400V3-phase(seegure4)butcanbereconnectedfor
230V3-phase.
Theinputcablingtothecontactorsshouldthenbefusedaccordingtothetableabove,seegure5+electricaldrawing.
NOTE!Ifreconnectionisperformed,thesuppliedalternativeratingplatemustbetted.
Theinputcablingforthecontactors(K1A-K4A)shallbeconnectedaccordingtotheelectricaldrawinginthewayshowningure
3below.NOTE! It is important that the screwdriver has the correct dimensions, and is pushed into the correct hole in
the correct way.