EasyManua.ls Logo

Pahlen MidiHeat EHA - Pipe Installation; Electrical Installation

Pahlen MidiHeat EHA
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10
MidiHeat EHA
MA45-32E
ENGLISH
1
4
2
3
5 5
11
9
7
6
8
10
12
13
10
1. Skimmer
2. Maindrain
3. Inlet
4.JetSwim
5. Light
6. Circulationpump
7. Filter
8. MidiHeat
9. Non-returnvalve
10.Drain
11. Bypass valve
12.Shut-offvalve
13. Draining valve
Figure2
Electrical installation
• Theelectricalinstallationmustbeperformedbyanauthorizedelectricianandinaccordancewiththeinstructionsincluded
withtheheater.
• Amainswitchmustbettedbeforealloftheheater’selectricalconnections(L1,L2L3).Thismustbeamulti-poleswitch
thatfullsthedemandsofIEC/EN60335-1sections7.12.2,22.2,24.3.
• Werecommendtheinstallationofaresidualcurrentdevice.
• Connecttheheaterinaccordancewiththeconnectiondrawing,seepages13and14.
• ThecontrolvoltageisconnectedtoconnectionblockL1andNfromasinglephase230VsupplyortoL1andL2froma
3-phase230VsupplywithnoN(neutral).
Notethatthecontrolvoltagemustbeequippedwithseparate5–10Afusesfortheelectricalconnections(L1,L2).
• Theheatermustbeinstalledinsuchawaythatitcannotbeactivatedunlesscirculationpump(sufcientow)isoperational,
i.e.thecontrolvoltagetotheheater’scontactormustbeinterlockedviathepump’scontactor.
• Donotconnecttheheatertoanincorrectpowersource.Contactthelocalelectricalutilityforthecorrectpowersource.
Thevoltagetotheheatermaynotvarybymorethan+5%to-10%withrespecttothemodelandnameplatespecication.
• Ondelivery,theheaterisconnectedfor400V3-phase,seegure4+electricaldrawingpage13,butcanbereconnectedfor
230V3-phase,seegure5+electricaldrawingpage14(appliestoallvariantsexcept72kW).
• Theinputcablingforthecontrolcircuitmustalwaysbefusedfor5–10A.
• Theinputcablingforthecontactorsshallbefusedinaccordancewiththetablefortheoperatingvoltageinquestion,
seegure4or5.
Installation
Piperoutingshallalwaysperformedbeforetheelectricalinstallation.
Positiontheheatersothatthefrontandtopcanbeopened.Installtheconnectionssothattheheatercanbeeasilymovedfor
inspection, cleaning and service.
Anon-returnvalvemustbeinstalledAFTERtheheaterandashut-offvalveBEFOREtheheatertoallowservicingtheheater
withoutneedingtoemptythepool.
Aby-passshouldbeinstalledandadjustedsothattherecommendedowthroughtheheatercanbeattained.
Mounttheheaterontheoor/foundationwithscrews/boltsthroughthefourØ9mmholesinthebottom.
Pipe installation
Connecttheheatertothepoolsystemaccordingtotheowdiagrambelow.Theoutletmustnotbeconnectedtoanyothertype
of tap or connection than those given.
TheelectricheaterhasaG2¾”connectionforgluedattachmentofØ63mmouterdiameterPVCpiping.
NOTE! Do not t a shut-off valve between the heater and swimming pool (t a non-return valve instead).
Mixingofchlorine,acidorsimilarinthepoolwatermustalwaysbeperformedAFTERtheheater,toavoidcorrosion.

Related product manuals