104 Aquarea air-to-water heat pumps - Planning and installation manual - 02/2022
Planning
5
Indoor oor area requirement for R32 models
Due to the classication of R32 with regard to safety, toxicity and ammability, limitations regarding
the refrigerant quantity in relation to the oor area must be observed based on the applicable
standards:
● If the total refrigerant charge in the system is <1.84 kg, no additional minimum oor
area is required.
● If the total refrigerant charge in the system is ≥1.84 kg, perform the following steps
to determine, if the room is large enough to install the indoor unit or if any additional
safety measures need to be taken.
Symbol Description Unit
m
c
Total refrigerant charge in system
where:
Total refrigerant charge in system, m
c
(kg) = Pre-charged refrigerant amount in unit (kg)
+ Additional refrigerant amount after installation (kg)
kg
m
max
Maximum allowed refrigerant charge kg
m
excess
Excess refrigerant charge quantity (m
c
– m
max
) kg
A
room
Floor area of the installation room m²
B
room
Floor area of the room adjacent to the installation room m²
H Installation height m
VA
min
Minimum ventilation opening area cm²
A
min total
Minimum required total oor area (A
room
+ B
room
) m²
Step A: Determine the maximum allowed refrigerant charge (m
max
):
1. Calculate the oor area of the installation room (A
room
).
2. Based on Table I (see below), select the maximum allowed refrigerant charge (m
max
), which
corresponds to the calculated A
room
value.
3. If the maximum allowed refrigerant charge is larger than the total refrigerant charge in
the system (m
max
> m
c
), the unit can be installed in the installation room at the installation
height of H = 600 mm, which is specied in Table I, and without additional oor area or any
additional ventilation.
4. If not (m
max
< m
c
), proceed to Step B and Step C, to determine how the oor area of the
installation room (A
room
) can be “enlarged” by the oor area of an adjacent room (B
room
) by
providing suciently large ventilation openings between the two rooms.
30.11.2021, cH
Can we name the relevant European standards?