56 Aquarea air-to-water heat pumps - Planning and installation manual - 02/2022
Product Description
4
Mono-bloc systems | Aquarea High Performance | H Generation | Single Phase | Heating and
Cooling | R410A
Single phase
Outdoor unit WH‑MDC12H6E5 WH‑MDC16H6E5
Heating capacity / COP (A +7 °C, W 35 °C) kW / – 12.00 / 4.74 16.00 / 4.28
Heating capacity / COP (A +7 °C, W 55 °C) kW / – 12.00 / 2.93 14.50 / 2.72
Heating capacity / COP (A +2 °C, W 35 °C) kW / – 11.40 / 3.44 13.00 / 3.28
Heating capacity / COP (A +2 °C, W 55 °C) kW / – 9.10 / 2.23 9.80 / 2.21
Heating capacity / COP (A -7 °C, W 35 °C) kW / – 10.00 / 2.73 11.40 / 2.57
Heating capacity / COP (A -7 °C, W 55 °C) kW / – 8.20 / 1.95 9.00 / 1.84
Cooling capacity / EER (A 35 °C, W 7 °C) kW / – 10.00 / 2.81 12.20 / 2.56
Cooling capacity / EER (A 35 °C, W 18 °C) kW / – 10.00 / 4.65 12.20 / 4.12
ErP data for Space Heating
Average climate
Seasonalenergyefciency(ηs,h) W35 / W55 % 190 / 134 190 / 130
SCOP W35 / W55 4.83 / 3.43 4.83 / 3.33
Energy class
1
W35 / W55 A+++ / A++ A+++ / A++
Warm climate
Seasonalenergyefciency(ηs,h) W35 / W55 % 245 / 159 245 / 169
SCOP W35 / W55 6.20 / 4.05 6.20 / 4.30
Energy class
1
W35 / W55 A+++ / A+++ A+++ / A+++
Cold climate
Seasonalenergyefciency(ηs,h) W35 / W55 % 168 / 121 168 / 121
SCOP W35 / W55 4.28 / 3.10 4.28 / 3.10
Energy class
1
W35 / W55 A++ / A+ A++ / A+
Sound power
2
Heat dB(A) 65 65
Dimension H x W x D mm 1,410 x 1,283 x 320 1,410 x 1,283 x 320
Net weight kg 140 140
Refrigerant (R410A) / CO
2
Eq.
3
kg / t 2.10 / 4.385 2.10 / 4.385
Water pipe connector Inch R 1¼ R 1¼
Pump
Number of speeds Variable Speed Variable Speed
Input power (Min / Max) W 34 / 110 38 / 120
Heatingwaterow(∆T=5K.35°C) l/min 34.4 45.9
Capacity of integrated electric heater kW 6 6
Input Power
Heat kW 2.53 3.74
Cool kW 3.56 4.76
Running and Starting
current
Heat A 11.7 16.9
Cool A 16.2 21.5
Current 1 A 24.0 26.0
Current 2 A 26.0 26.0
Recommended fuse A 30 / 30 30 / 30
Recommended cable size, supply 1 / 2 mm² 3 x 4.0 or 6.0 / 3 x 4.0 3 x 4.0 or 6.0 / 3 x 4.0
Operation range
Outdoor ambient
Heat °C -20 ~ +35 -20 ~ +35
Cool °C +16 ~ +43 +16 ~ +43
Water outlet
Heat °C 25 ~ 55 25 ~ 55
Cool °C 5 ~ 20 5 ~ 20
1 Scale from A+++ to D.
2 Sound power in accordance to 811/2013, 813/2013 and EN12102-1:2017 at +7 °C.
3 WH-MDC models are hermetically sealed.
Note:
EER and COP calculation is based in accordance to EN14511.