Aquarea air-to-water heat pumps - Planning and installation manual - 02/2022
Planning
5
Table I: Maximum refrigerant charge allowed in a room
A
room
(m²) Maximum refrigerant
charge (m
max
) (kg)
A
room
(m²) Maximum refrigerant
charge (m
max
) (kg)
A
room
(m²) Maximum refrigerant
charge (m
max
) (kg)
H = 0.6 m H = 0.6 m H = 0.6 m
1 0.138 16 1.371 31 1.909
2 0.276 17 1.413 32 1.939
3 0.414 18 1.454 33 1.969
4 0.553 19 1.494 34 1.999
5 0.691 20 1.533 35 2.028
6 0.829 21 1.571 36 2.057
7 0.907 22 1.608 37 2.085
8 0.970 23 1.644 38 2.113
9 1.028 24 1.679 39 2.141
10 1.084 25 1.714 40 2.168
11 1.137 26 1.748 41 2.195
12 1.187 27 1.781 42 2.221
13 1.236 28 1.814 43 2.248
14 1.283 29 1.846 44 2.274
15 1.328 30 1.877
Notes:
For H values lower than 0.6 m, the value of H is to be considered as 0.6 m to comply to IEC 60335-2-40:2018 Clause GG2.
For intermediate A
room
values, the value that corresponds to the lower A
room
value from the table is to be considered.
Example: For A
room
= 10.5 m², the value that corresponds to “A
room
= 10 m²” is to be considered.
Step B: Determine compliance of total oor area (A
room
+ B
room
) to minimum required total oor area
(A
min total
):
1. Calculate the oor area (B
room
) of the room adjacent to the installation room.
2. Determine the minimum required total oor area (A
min total
) based on the total refrigerant
charge (m
c
) as specied in Table II (see below).
3. If the total oor area of both rooms (A
room
+ B
room
) exceeds the minimum required total oor
area (A
min total
), proceed to Step C, to determine how large the ventilation openings between
the two rooms must be. If not, the unit must not be installed.
Table II: Minimum allowed total oor area
m
c
(kg) Minimum oor area
(A
min total
) (m²)
m
c
(kg) Minimum oor area
(A
min total
) (m²)
m
c
(kg) Minimum oor area
(A
min total
) (m²)
H = 0.6 m H = 0.6 m H = 0.6 m
1.84 28.81 2.00 34.04 2.16 39.71
1.86 29.44 2.02 34.73 2.18 40.45
1.88 30.08 2.04 35.42 2.20 41.19
1.90 30.72 2.06 36.12 2.22 41.94
1.92 31.37 2.08 36.82 2.24 42.70
1.94 32.03 2.10 37.53 2.26 43.47
1.96 32.70 2.12 38.25 2.27 43.86
1.98 33.37 2.14 38.98
Notes:
For H values lower than 0.6 m, the value of H is to be considered as 0.6 m to comply to IEC 60335-2-40:2018 Clause GG2.
For intermediate m
c
values, the value that corresponds to the higher m
c
value from the table is to be considered.
Example: If m
c
= 1.85 kg, the value that corresponds to “m
c
= 1.86 kg” is to be considered.
Systems with total refrigerant charge lower than 1.84 kg are not subjected to any oor area requirements.
Charges above 2.27 kg are not allowed in the unit.