42 Aquarea air-to-water heat pumps - Planning and installation manual - 02/2022
Product Description
4
All in One Compact systems | Aquarea High Performance | J Generation | Single Phase | Heating and
Cooling | R32
Single phase (Power to indoor)
Kit KIT‑ADC03JE5C KIT‑ADC05JE5C KIT‑ADC07JE5C KIT‑ADC09JE5C‑1
Heating capacity / COP (A +7 °C, W 35 °C) kW / – 3.20 / 5.33 5.00 / 5.00 7.00 / 4.76 9.00 / 4.48
Heating capacity / COP (A +7 °C, W 55 °C) kW / – 3.20 / 2.81 5.00 / 2.72 7.00 / 2.82 8.95 / 2.78
Heating capacity / COP (A +2 °C, W 35 °C) kW / – 3.20 / 3.64 4.20 / 3.18 6.85 / 3.41 7.00 / 3.40
Heating capacity / COP (A +2 °C, W 55 °C) kW / – 3.20 / 2.19 4.10 / 1.99 6.20 / 2.21 6.30 / 2.16
Heating capacity / COP (A -7 °C, W 35 °C) kW / – 3.30 / 2.80 4.20 / 2.59 5.60 / 2.87 6.12 / 2.78
Heating capacity / COP (A -7 °C, W 55 °C) kW / – 3.20 / 1.79 3.55 / 1.71 5.25 / 1.94 5.90 / 1.93
Cooling capacity / EER (A 35 °C, W 7 °C) kW / – 3.20 / 3.52 4.50 / 3.00 6.70 / 3.03 8.20 / 2.72
Cooling capacity / EER (A 35 °C, W 18 °C) kW / – 3.20 / 4.71 4.80 / 4.29 6.70 / 4.72 9.00 / 4.18
ErP data for Space Heating
Average climate
Seasonalenergyefciency(ηs,h) W35 / W55 % 200 / 136 200 / 136 193 / 130 193 / 130
SCOP W35 / W55 5.07 / 3.47 5.07 / 3.47 4.90 / 3.32 4.90 / 3.32
Energy class
1
W35 / W55 A+++ / A++ A+++ / A++ A+++ / A++ A+++ / A++
Warm climate
Seasonalenergyefciency(ηs,h) W35 / W55 % 245 / 165 245 / 165 227 / 160 227 / 160
SCOP W35 / W55 6.20 / 4.20 6.20 / 4.20 5.75 / 4.07 5.75 / 4.07
Energy class
1
W35 / W55 A+++ / A+++ A+++ / A+++ A+++ / A+++ A+++ / A+++
Cold climate
Seasonalenergyefciency(ηs,h) W35 / W55 % 157 / 110 157 / 110 164 / 116 164 / 116
SCOP W35 / W55 4.00 / 2.83 4.00 / 2.83 4.18 / 2.98 4.18 / 2.98
Energy class
1
W35 / W55 A++ / A+ A++ / A+ A++ / A+ A++ / A+
Indoor unit WH‑ADC0309J3E5C WH‑ADC0309J3E5C WH‑ADC0309J3E5C WH‑ADC0309J3E5C
Sound pressure Heat / Cool dB(A) 28 / 28 28 / 28 28 / 28 28 / 28
Dimension H x W x D mm 1,640 x 598 x 600 1,640 x 598 x 600 1,640 x 598 x 600 1,640 x 598 x 600
Net weight kg 101 101 101 101
Water pipe connector Inch R 1¼ R 1¼ R 1¼ R 1¼
A class pump
Number of speeds Variable Speed Variable Speed Variable Speed Variable Speed
Input power (Min / Max) W 30 / 120 30 / 120 30 / 120 30 / 120
Heatingwaterow(∆T=5K.35°C) l/min 9.20 14.30 20.10 25.80
Capacity of integrated electric heater kW 3.00 3.00 3.00 3.00
Recommended fuse A 16 / 16 16 / 16 25 / 16 25 / 16
Recommended cable size, supply 1 / 2 mm² 3 x 1.5 / 3 x 1.5 3 x 1.5 / 3 x 1.5 3 x 2.5 / 3 x 1.5 3 x 2.5 / 3 x 1.5
Water volume l 185 185 185 185
Maximum water temperature °C 65 65 65 65
Material inside tank Stainless steel Stainless steel Stainless steel Stainless steel
TappingproleaccordingEN16147 L L L L
ErP data for Water Heating
Average climate
Seasonalenergyefciency(ηw,h) % 128 128 116 116
SCOP 3.20 3.20 2.90 2.90
Energy class
2
A+ A+ A+ A+
Warm climate
Seasonalenergyefciency(ηw,h) % 154 154 134 134
SCOP 3.86 3.86 3.35 3.35
Energy class
2
A+ A+ A+ A+
Cold climate
Seasonalenergyefciency(ηw,h) % 99 99 98 98
SCOP 2.48 2.48 2.45 2.45
Energy class
2
A A A A
Outdoor unit WH‑UD03JE5 WH‑UD05JE5 WH‑UD07JE5 WH‑UD09JE5‑1
Sound power
3
Heat dB(A) 55 55 59 59
Dimension / Net weight H x W x D mm / kg 622 x 824 x 298 / 37 622 x 824 x 298 / 37 795 x 875 x 320 / 61 795 x 875 x 320 / 61
Refrigerant (R32) / CO
2
Eq. kg / T 0.9 / 0.608 0.9 / 0.608 1.27 / 0.857 1.27 / 0.857
Pipe diameter Liquid / Gas Inch (mm) 1/4 (6.35) / 1/2 (12.70) 1/4 (6.35) / 1/2 (12.70) 1/4 (6.35) / 5/8 (15.88) 1/4 (6.35) / 5/8 (15.88)
Pipe length range / Elevation difference (in/out) m / m 3 ~ 25 / 20 3 ~ 25 / 20 3 ~ 50 / 30 3 ~ 50 / 30
Pipe length for additional gas / Additional gas amount m / g/m 10 / 20 10 / 20 10 / 25 10 / 25
Operation range
Outdoor ambient
Heat °C -20 ~ +35 -20 ~ +35 -20 ~ +35 -20 ~ +35
Cool °C +10 ~ +43 +10 ~ +43 +10 ~ +43 +10 ~ +43
Water outlet
Heat °C 20 ~ 60 20 ~ 60 20 ~ 60 20 ~ 60
Cool °C 5 ~ 20 5 ~ 20 5 ~ 20 5 ~ 20
1 Scale from A+++ to D.
2 Scale from A+ to F.
3 Sound power in accordance to 811/2013, 813/2013 and EN12102-1:2017 at +7 °C.
Notes:
EER and COP calculation is based in accordance to EN14511.
This product is designed to comply with the European Water Quality Directive 98/83/EC amended by 2015/1787/EU. The lifespan of the product is not guaranteed in the case of the use of
groundwater, such as spring water or well water, the use of tap water when salt or other impurities are contained, nor in areas of acidic water quality. Maintenance and warranty costs related to
these cases are the customer’s responsibility.