44 Aquarea air-to-water heat pumps - Planning and installation manual - 02/2022
Product Description
4
All in One systems | Aquarea T-CAP | H Generation | Single Phase / Three Phase | Heating and
Cooling | R410A
Single phase (Power to indoor) Three phase (Power to indoor)
Kit KIT‑AXC09HE5 KIT‑AXC12HE5 KIT‑AXC09HE8 KIT‑AXC12HE8 KIT‑AXC16HE8
Heating capacity / COP (A +7 °C, W 35 °C) kW / – 9.00 / 4.84 12.00 / 4.74 9.00 / 4.84 12.00 / 4.74 16.00 / 4.28
Heating capacity / COP (A +7 °C, W 55 °C) kW / – 9.00 / 2.94 12.00 / 2.88 9.00 / 2.94 12.00 / 2.88 16.00 / 2.71
Heating capacity / COP (A +2 °C, W 35 °C) kW / – 9.00 / 3.59 12.00 / 3.44 9.00 / 3.59 12.00 / 3.44 16.00 / 3.10
Heating capacity / COP (A +2 °C, W 55 °C) kW / – 9.00 / 2.21 12.00 / 2.19 9.00 / 2.21 12.00 / 2.19 16.00 / 2.13
Heating capacity / COP (A -7 °C, W 35 °C) kW / – 9.00 / 2.85 12.00 / 2.72 9.00 / 2.85 12.00 / 2.72 16.00 / 2.49
Heating capacity / COP (A -7 °C, W 55 °C) kW / – 9.00 / 2.02 12.00 / 1.92 9.00 / 2.02 12.00 / 1.92 16.00 / 1.86
Cooling capacity / EER (A 35 °C, W 7 °C) kW / – 7.00 / 3.17 10.00 / 2.81 7.00 / 3.17 10.00 / 2.81 12.20 / 2.57
Cooling capacity / EER (A 35 °C, W 18 °C) kW / – 7.00 / 5.19 10.00 / 5.13 7.00 / 5.19 10.00 / 5.13 12.20 / 3.49
ErP data for Space Heating
Average climate
Seasonalenergyefciency(ηs,h) W35 / W55 % 181 / 130 170 / 130 181 / 130 170 / 130 160 / 125
SCOP W35 / W55 4.59 / 3.32 4.32 / 3.32 4.59 / 3.32 4.32 / 3.32 4.08 / 3.20
Energy class
1
W35 / W55 A+++ / A++ A++ / A++ A+++ / A++ A++ / A++ A++ / A++
Warm climate
Seasonalenergyefciency(ηs,h) W35 / W55 % 235 / 158 231 / 158 235 / 158 231 / 158 231 / 159
SCOP W35 / W55 5.95 / 4.02 5.86 / 4.02 5.95 / 4.02 5.86 / 4.02 5.86 / 4.05
Energy class
1
W35 / W55 A+++ / A+++ A+++ / A+++ A+++ / A+++ A+++ / A+++ A+++ / A+++
Cold climate
Seasonalenergyefciency(ηs,h) W35 / W55 % 160 / 125 160 / 125 160 / 125 160 / 125 150 / 125
SCOP W35 / W55 4.08 / 3.20 4.08 / 3.20 4.08 / 3.20 4.08 / 3.20 3.83 / 3.20
Energy class
1
W35 / W55 A++ / A++ A++ / A++ A++ / A++ A++ / A++ A++ / A++
Indoor unit WH‑ADC1216H6E5 WH‑ADC1216H6E5 WH‑ADC0916H9E8 WH‑ADC0916H9E8 WH‑ADC0916H9E8
Sound pressure Heat / Cool dB(A) 33 / 33 33 / 33 33 / 33 33 / 33 33 / 33
Dimension H x W x D mm 1,800 x 598 x 717 1,800 x 598 x 717 1,800 x 598 x 717 1,800 x 598 x 717 1,800 x 598 x 717
Net weight kg 124 124 126 126 126
Water pipe connector Inch R 1¼ R 1¼ R 1¼ R 1¼ R 1¼
A class pump
Number of speeds Variable Speed Variable Speed Variable Speed Variable Speed Variable Speed
Input power (Min / Max) W 36 / 152 36 / 152 36 / 152 36 / 152 36 / 152
Heatingwaterow(∆T=5K.35°C) l/min 25.8 34.4 25.8 34.4 45.9
Capacity of integrated electric heater kW 6 6 9 9 9
Recommended fuse A 30 / 30 30 / 30 16 / 16 16 / 16 16 / 16
Recommended cable size, supply 1 / 2 mm² 3 x 4.0 / 3 x 4.0 3 x 4.0 / 3 x 4.0 5 x 1.5 / 5 x 1.5 5 x 1.5 / 5 x 1.5 5 x 1.5 / 5 x 1.5
Water volume l 185 185 185 185 185
Maximum water temperature °C 65 65 65 65 65
Material inside tank Stainless steel Stainless steel Stainless steel Stainless steel Stainless steel
TappingproleaccordingEN16147 L L L L L
ErP data for Water Heating
Average climate
Seasonalenergyefciency(ηw,h) % 95 95 95 95 91 /
SCOP 2.37 2.37 2.37 2.37 2.27
Energy class
2
A A A A A
Warm climate
Seasonalenergyefciency(ηw,h) % 110 110 110 110 / 107
SCOP 2.75 2.75 2.75 2.75 2.67
Energy class
2
A A A A A
Cold climate
Seasonalenergyefciency(ηw,h) % 75 75 75 75 72
SCOP 1.87 1.87 1.87 1.87 1.80
Energy class
2
A A A A B
Outdoor unit WH‑UX09HE5 WH‑UX12HE5 WH‑UX09HE8 WH‑UX12HE8 WH‑UX16HE8
Sound power
3
Heat dB(A) 66 66 65 65 67
Dimension / Net weight H x W x D mm / kg 1,340 x 900 x 320 / 101 1,340 x 900 x 320 / 101 1,340 x 900 x 320 / 108 1,340 x 900 x 320 / 108 1,340 x 900 x 320 / 118
Refrigerant (R410A) / CO
2
Eq. kg / t 2.85 / 5.951 2.85 / 5.951 2.85 / 5.951 2.85 / 5.951 2.90 / 6.055
Pipe diameter Liquid / Gas Inch (mm) 3/8 (9.52) / 5/8 (15.88) 3/8 (9.52) / 5/8 (15.88) 3/8 (9.52) / 5/8 (15.88) 3/8 (9.52) / 5/8 (15.88) 3/8 (9.52) / 5/8 (15.88)
Pipe length range / Elevation difference (in/out) m / m 3 ~ 30 / 20 3 ~ 30 / 20 3 ~ 30 / 20 3 ~ 30 / 20 3 ~ 30 / 20
Pipe length for additional gas / Additional gas amount m / g/m 10 / 50 10 / 50 10 / 50 10 / 50 10 / 50
Operation range
Outdoor ambient
Heat °C -28 ~ +35 -28 ~ +35 -28 ~ +35 -28 ~ +35 -28 ~ +35
Cool °C +16 ~ +43 +16 ~ +43 +16 ~ +43 +16 ~ +43 +16 ~ +43
Water outlet
Heat °C 20 ~ 60 20 ~ 60 20 ~ 60 20 ~ 60 20 ~ 60
Cool °C 5 ~ 20 5 ~ 20 5 ~ 20 5 ~ 20 5 ~ 20
1 Scale from A+++ to D.
2 Scale from A+ to F.
3 Sound power in accordance to 811/2013, 813/2013 and EN12102-1:2017 at +7 °C.
Notes:
EER and COP calculation is based in accordance to EN14511.
This product is designed to comply with the European Water Quality Directive 98/83/EC amended by 2015/1787/EU. The lifespan of the product is not guaranteed in the case of the use of
groundwater, such as spring water or well water, the use of tap water when salt or other impurities are contained, nor in areas of acidic water quality. Maintenance and warranty costs related to
these cases are the customer’s responsibility.