89
Aquarea air-to-water heat pumps - Planning and installation manual - 02/2022
Product Description
4
Dimensions
PAW‑A2W‑VENTA‑L/‑R PAW‑A2W‑VENTA‑L PAW‑A2W‑VENTA‑R
Left side view Front view Front view
500
470
99 99
99 99
118 109
118109
97
97
116
108 109
171
139116
598
450
598
450
PAW‑A2W‑VENTA‑L PAW‑A2W‑VENTA‑R
Top view Top view
99 99
99 99
118 109
118109
97
97
116
108 109
171
139116
Ø125(x4)
Ø125(x4)
Unit: mm
Technical data
Heat recovery Ventilation unit PAW-A2W-VENTA-L PAW-A2W-VENTA-R
Supply side Left Right
Nominalairowrate@50Pa m³/h 204
Maximumairowrate@100Pa m³/h 292
Specicfanpower(SFP)@204m³/h 1.24
Heat exchanger rotor drive type Variable speed
Exchanger type Rotating
Heatrecoveryefciency1 84 %
Power supply V / Ph / Hz 230 / 1 / 50
Power consumption W 176
Energy Class, basic unit A
Energy Class, unit with local control on demand A
Noise level dB(A) 40
Dimension (W x H x D) mm 598 x 450 x 500
Weight kg 46
Mounting position Vertical