64 Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
Product Description
65
Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
Product Description
Terminals Connection Function Condition Cable cross
section
CN205
5 to 6
Temperature
sensor for buffer tank
PAW-A2W-TSBU
For measuring the buffer tank
temperature
Maximum total cable length: 30 m 2×min.
0.3mm²
CN206
2 to 4
SG-Signal SmartGridswitch
Dry contact, Vcc-Bit1, Vcc-Bit2, Open /
Closed
Mustbeconnectedtobothcontacts.
Systemsettingneeded.
Maximum total cable length: 50 m
3×min.
0.3mm²
CN207
1 to 2
Power control signal 0–10VDCsignal. Mustbeconnectedto0-10VDCcontrol.
Systemsettingneeded.
Maximum total cable length: 50 m
2×min.
0.3mm²
CN207
3 to 4
Solar temperature sen-
sor PAW-A2W-TSSO
For measuring the solar module
temperature
Maximum total cable length: 30 m 2×min.
0.3mm²
CN208
1 to 2
PumpheatC.1 230 V AC, <500 W Maximum total cable length: 50 m 2×min.
1.5mm²
CN208
3 to 4
PumpheatC.2
CN209
1 to 2
Swimming pool pump 230 V AC Maximum total cable length: 50 m 2×min.
1.5mm²
CN209
3 to 4
Solar station 230 V AC Maximum total cable length: 50 m 2×min.
1.5mm²
CN209
5 to 6
Fault reporting signal
CN210
1 to 2
External compressor
switch
Dry contact, Open = Outdoor unit ON,
Closed = Outdoor unit OFF
Systemsettingneeded.
Maximum total cable length: 50 m
2×min.
0.3mm²
CN210
3 to 4
Heating/ Cooling
Switch
Dry contact, Open = Heating, Closed =
Cooling
Systemsettingneeded.
Maximum total cable length: 50 m
2×min.
0.3mm²
Connection conditions
The connection of the optional PCB allows temperature control for two heating circuits. Mixing
valves, circulation pumps and temperature sensors for heating circuits 1 and 2 are to be con-
nected to the corresponding terminals of the optional additional PCB. The temperatures in the
two heating circuits are controlled mutually independently by the operating unit.
Pumps for Heating Circuits 1 and 2:
The cables of the pumps for heating circuits 1 and 2 must each be 2 x min.
1.5 mm
2
and conform to the code 60245 IEC 57 or higher.
Maximum total cable length: 50 m
Solar station:
The cable of the solar station must be 2 x min. 1.5 mm² and conform to the code
60245 IEC 57 or higher.
Maximum total cable length: 50 m
Swimming pool pump:
The cable of the swimming pool pump must be 2 x min. 1.5 mm² and conform to
the code 60245 IEC 57 or higher.
Maximum total cable length: 50 m
Additional PCB CZ-NS4P
Overview of the External Interfaces
Vcc
Bit1
Bit2
N O CN O CL N Cool Heat L N Cool Heat
CN206
CN205
CN203CN202CN201
CN204 CN207
CN208 CN209
CN210
1 1 1
11 1
1
1
1
1
2
2
2
2
3
3
3
3
4
4
4
4
5
6
2 2 2
22 2
3 3 3
33 3
4 4 4
44 4
5
55
6
66
Optional thermostat 2 Optional Thermostat 1 Mixing valve 1 Mixing valve 2
External compressor
switch
Heating/ Cooling Switch
SG-Signal
Swimming pool pump
Solar station
Fault reporting signal
PumpheatC.1
PumpheatC.2
Room temperature
sensorheatC.2
Water temperature
sensorheatC.2
Water temperature
sensorheatC.1
Power control signal
Solar temperature sensor
Room temperature
sensorheatC.1
Temperature sensor for
buffer tank
Temperature sensor for
swimming pool
Terminals Connection Function Condition Cable cross
section
CN201
1 to 4
Optional thermostat 2 Heating / cooling requirement of
thermostats.
LN=230VAC,Heat=heating,
Cool = cooling
Maximum total cable length: 50 m 4×min.
0.5mm²
CN202
1 to 4
Optional Thermostat 1
CN203
1 to 3
Mixing valve 1 230 V AC, N = Neutral, O = Open,
C = Closed = Direction reversal
Actuation duration: 30 to 120 s
Maximum total cable length: 50 m 3×min.
1.5mm²
CN203
4 to 6
Mixing valve 2
CN204
1 to 2
Temperature sensor
for swimming pool
PAW-A2W-TSHC
Maximum total cable length: 30 m 2×min.
0.3mm²
CN204
3 to 4
Infeed temperature
sensorheatC.2
PAW-A2W-TSHC
For measuring the water temperature in
the respective heating circuit
Maximum total cable length: 30 m 2×min.
0.3mm²
CN204
5 to 6
Infeed temperature
sensorheatC.1
PAW-A2W-TSHC
CN205
1 to 2
Room temperature
sensorheatC.2
PAW-A2W-TSRT
Maximum total cable length: 30 m 2×min.
0.3mm²
CN205
3 to 4
Room temperature
sensorheatC.1
PAW-A2W-TSRT

Table of Contents

Related product manuals