206 Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
Appendix
207
Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
Appendix
Menu Standard setting Setting options /Display
1.2
Holiday timer
To save energy, a holiday period
can be set which enables the
system either to be switched
off or for the temperature to be
reduced in this period.
OFF
ON
Beginning and end of holiday.
Date and time
OFF or reduced temperature
The weekly timer setting can be deactivated during holiday timer setting, but is then
reactivated as soon as the holiday timer has expired.
1.3
Quiet timer
For reducing the noise level during the
set period of time.
6 programmes can be set.
Stage 0 means that the quiet
mode has been deactivated.
Starting time for the quiet mode:
Date and time
Quiet mode stage:
0 to 3
1.4
E-heating element heating
Activating the electric heating
element for the heating mode.
OFF
1.5
E-heating element for hot water
Activating the electric heating
element for the hot water mode.
OFF
Only available if a connection with the hot water tank is in place.
1.6
Sterilisation
Activation or deactivation of
automatic sterilisation.
OFF
Only available if a connection with the hot water tank is in place.
Do not use the system during sterilisation so as to avoid scalding by hot water.
To set the sterilisation function in accordance with the local laws and regulations in force, please contact your
authorised installer or service partner.
2 System monitoring
2.1
Energy monitor
Diagram with current or recorded
data on energy consumption,
generation or COP.
Current data
Select and retrieve
Recording
Select and retrieve
COP = coefficient of performance
Periods covered in the diagrams with recorded data: 1 day / 1 week / 1 year
Energy consumption can be retrieved in kWh for heating mode, cooling mode *
1
and hot water mode as well as overall energy consumption.
Overall electricity consumption involves an estimated value based on 230 V alternating
current. It can deviate from the value measured using precision equipment.
2.2
Water temperatures
Display of the different current
water temperatures.
Current values of 8 water temperatures:
Return flow / inflow / HC 1 / HC 2
hot water tank / buffer tank / solar /
swimming pool
Select and retrieve
Menus
For users
*1 The system is preset for operation without a cooling function. The cooling function can be activated by an authorised installer or service partner.
*2 This display only appears if the cooling function is activated, i.e. if the cooling mode is available.
Menus
For users
The menu items and settings to be used depend on the heating system
present in each case. All basic settings are to be undertaken by an
authorised installer or service partner and should also only be altered by
such a person.
Once the basic settings have been made, the settings can be adjusted
manually.
The basic settings will remain active until they are altered.
The operating unit can be used for different systems.
In order to be able to make settings, the operating LED must not be
illuminated.
Incorrect settings can lead to impaired functioning of the heating system.
In such a case, contact your authorised installer or service partner.
Displaying the “Main menu”:
Selecting a menu item:
Confirming the menu item selected:
In addition to the basic settings, further settings can be made via the Quick menu.
1
Press
to display the Quick menu
Manual
hot water
preparation
Power mode Quiet mode Heating, always on
Weekly timer Manual defrost mode Error reset
Locking the operating
unit
2
Select the Menu by using
.
3
Press
to switch on or off, or to set, the function selected.
Quick menu
Menu Standard setting Setting options /Display
1 Function setting
1.1
Weekly timer
As soon as the weekly timer has
been set, the user can adjust this via
the Quick menu.
Up to 6 switching programmes can
be set per day.
The weekly timer is deactivated
if the cooling/heating switch is
activated or the emergency heating
mode is switched on.
Setting the timer
Select the day of the week and set the
programme desired.
(Switching time / On/Off / operating mode)
Copying the timer
Select the day of the week.