38 Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
Product Description
39
Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
Product Description
Split systems with combination hydro-module / LT series / H Generation (contd.)
LT series Three-phase (400 V / 50 Hz), heating and cooling
Combined Hydro-module WH-ADC0916H9E8
Outdoor unit WH-UD09HE8 WH-UD12HE8 WH-UD16HE8
Set (Combination Hydro-module + outdoor unit) KIT-ADC9HE8 KIT-ADC12HE8 KIT-ADC16HE8
Model B3 B3 B3
Heatingcapacityat+7°C(A7/W35) kW 9.00 12.00 16.00
COPat+7°C(A7/W35) 4.84 4.74 4.28
Heatingcapacityat+2°C(A2/W35) kW 9.00 11.40 13.00
COPat+2°C(A2/W35) 3.59 3.44 3.28
Heating capacity at -7 °C (A-7/W35) kW 9.00 10.00 11.40
COP at -7 °C (A-7/W35) 2.85 2.73 2.57
Energyefciencyclass
1
at 35 / 55 °C
i / i i / i i / i
Compositeenergyefciencyclass
2
at 35 / 55 °C
j / i j / i j / i
Cooling capacity at 35 °C (A35/W7) kW 7.00 10.00 12.20
EER at 35 °C (A35/W7) 3.17 2.85 2.56
Combined Hydro-module
Sound pressure level Heating / Cooling dB(A) 33 / 33 33 / 33 33 / 33
Dimensions HxLxW mm 1,800 x 598 x 717 1,800 x 598 x 717 1,800 x 598 x 717
Weight kg 139 139 139
Water-side connection mm 28 28 28
Highefciencypump
Rotation speed stages Variable Variable Variable
Powerconsumption(min./max.)
W 36 / 152 36 / 152 36 / 152
Waterowrate(A7/W35) l/min 25.8 34.4 45,9
Power of E-heating element kW 9 9 9
Power consumption Heating / Cooling kW 1.86/2.21 2.53/3.51 3.74/4.76
Operating and start up current Heating / Cooling A 2.8/3.4 3.8/5.3 5.7/7.1
Max.powerconsumptiononnetworkconnection1/2 A 7.5/13.0 8.8/13.0 9.9/13.0
Recommended fuse for network connection 1 / 2 A 16 / 16 16 / 16 16 / 16
Recommended cable cross section for network connection 1 / 2
mm² 5x1.5/5x1.5 5x1.5/5x1.5 5x1.5/5x1.5
Domestic hot water tank
Tank volume l 185 185 185
Max.watertemperature °C 65 65 65
Energyefciencyclass
3
at 55 °C
a a a
Material of the tank interior Stainless steel Stainless steel Stainless steel
Outdoor unit
Sound pressure level Heating / Cooling dB(A) 51 / 49 52 / 50 55 / 54
Dimensions HxLxW mm 1,340 x 900 x 320 1,340 x 900 x 320 1,340 x 900 x 320
Weight kg 108 108 108
Linediameter Fluid line mm (inches) 9.52(3/8) 9.52(3/8) 9.52(3/8)
Gasline mm (inches) 15.88(5/8) 15.88(5/8) 15.88(5/8)
Pre-lledrefrigerant(R410A)/CO
2
-equivalent kg / t CO
2
-Equ. 2.55/5.324 2.55/5.324 2.55/5.324
Connection distance m 3 – 30 3 – 30 3 – 30
Nominal connection distance m 7 7 7
Pre-lledconnectiondistance m 10 10 10
Additionalcoolantll-upquantity(R410A) g/m 50 50 50
Max.heightdifferenceIU/OU m 20 20 20
Operating range
Outside temperature (H / K) °C -20 to 35 / 16 to 43 -20 to 35 / 16 to 43 -20 to 35 / 16 to 43
Water outlet temperature (H / K)
°C 25 to 55 / 5 to 20 25 to 55 / 5 to 20 25 to 55 / 5 to 20
The COP details relate to 230 V in conformance with the EC Directives 2003/32/EC. Power details in conformance with EN 14511.
The information about the energy efciency classes is based on the ofcial ErP specications (EU Ordinance No. 811/2013, EN 14511 and EN 14825) for heat pumps, which have been in
force since 26. September 2015. The efciency classes marked with an asterisk (*) correspond to the new A+++ class to be introduced from September 2019. Other ErP relevant informa-
tion is included in the respective product data sheets.
Authorised Service Partners or installation companies can activate the cooling function via a special setting.
1 Energy efciency class scale from A++ to G.
2 Energy efciency class including controller. Energy efciency class scale from A+++ to D.
3 Energy efciency class scale from A to G.
4.6.2.3 Technical Data
Split systems with combination Hydro-module / LT series / H Generation
LT series Single-phase (230 V / 50 Hz), Heating and Cooling
Combined Hydro-module
WH-ADC0309H3E5
WH-ADC0309H3E5B
1
WH-ADC1216H6E5
Outdoor unit WH-UD03HE5-1 WH-UD05HE5-1 WH-UD07HE5-1 WH-UD09HE5-1 WH-UD12HE5 WH-UD16HE5
Set (Combination Hydro-module + outdoor unit) KIT-ADC03H3E5(B) KIT-ADC05H3E5(B) KIT-ADC07H3E5(B) KIT-ADC09H3E5(B) KIT-ADC12HE5 KIT-ADC16HE5
Model B1 B1 B2 B2 B3 B3
Heatingcapacityat+7°C(A7/W35) kW 3.20 5.00 7.00 9.00 12.00 16.00
COPat+7°C(A7/W35) 5.00 4.63 4.46 4.13 4.74 4.28
Heatingcapacityat+2°C(A2/W35) kW 3.20 4.20 6.55 6.70 11.40 13.00
COPat+2°C(A2/W35) 3.56 3.11 3.34 3.13 3.44 3.28
Heating capacity at -7 °C (A-7/W35) kW 3.20 4.20 5.15 5.90 10.00 11.40
COP at -7 °C (A-7/W35) 2.69 2.59 2.68 2.52 2.73 2.68
Energyefciencyclass
2
at 35 / 55 °C
i* / i i* / i i* / i i* / i i / i i / i
CompositeEnergyefciencyclass
3
at 35 / 55 °C
j / i j / i j / i j / i j / i j / i
Cooling capacity at 35 °C (A35/W7) kW 3.20 4.50 6.00 7.00 10.00 12.20
EER at 35 °C (A35/W7) 3.08 2.69 2.63 2.43 2.81 2.56
Combined Hydro-module
Sound pressure level Heating / Cooling dB(A) 28 / 28 28 / 28 28 / 28 28 / 28 33 / 33 33 / 33
Dimensions HxLxW mm 1,800 x 598 x 717 1,800 x 598 x 717 1,800 x 598 x 717 1,800 x 598 x 717 1,800 x 598 x 717 1,800 x 598 x 717
Weight kg 135 135 135 135 137 137
Water-side connection mm 28 28 28 28 28 28
Highefciencypump
Rotation speed stages Variable Variable Variable Variable Variable Variable
Powerconsumption(min./max.)
W 30 / 120 30 / 120 30 / 120 30 / 120 36 / 152 36 / 152
Waterowrate(A7/W35) l/min 9.2 14.3 20.1 25.8 34.4 45,9
Power of E-heating element kW 3 3 3 3 6 6
Power consumption Heating / Cooling kW 0.64/1.04 1.08/1.67 1.57/2.28 2.18/2.88 2.53/3.56 3.74/4.76
Operating and start up current Heating / Cooling A 3.0/4.8 5.0/7.6 7.2/10.3 10.0/13.0 11.5/16.0 16.9/21.3
Max.powerconsumptiononnetworkconnection1/2 A 12.0/13.0 12.0/13.0 21.0/13.0 22.9/13.0 24.0/26.0 26.0/26.0
Recommended fuse for network connection 1 / 2 A 15 / 15 15 / 15 30 / 15 30 / 15 30 / 30 30 / 30
Recommended cable cross section for network connection 1 / 2
mm² 3x1.5/3x1.5 3x1.5/3x1.5 3x2.5/3x1.5 3x2.5/3x1.5 3x4.0/3x4.0 3x4.0/3x4.0
Domestic hot water tank
Tank volume l 185 185 185 185 185 185
Max.watertemperature °C 65 65 65 65 65 65
Energyefciencyclass
4
at 55 °C
a a a a a a
Material of the tank interior Stainless steel Stainless steel Stainless steel Stainless steel Stainless steel Stainless steel
Outdoor unit
Sound pressure level Heating / Cooling dB(A) 48 / 47 49 / 48 50 / 48 51 / 50 52 / 50 55 / 54
Dimensions HxLxW mm 622 x 824 x 298 622 x 824 x 298 795 x 900 x 320 795 x 900 x 320 1,340 x 900 x 320 1,340 x 900 x 320
Weight kg 39 39 66 66 101 101
Linediameter Fluid line mm (inches) 6.35(1/4) 6.35(1/4) 6.35(1/4) 6.35(1/4) 9.52(3/8) 9.52(3/8)
Gasline mm (inches) 12.7(1/2) 12.7(1/2) 15.88(5/8) 15.88(5/8) 15.88(5/8) 15.88(5/8)
Pre-lledrefrigerant(R410A)/CO
2
-equivalent kg / t CO
2
-Equ. 1.20/2.506 1.20/2.506 1.45/3.028 1.45/3.028 2.55/5.324 2.55/5.324
Connection distance m 3 – 15 3 – 15 3 – 30 3 – 30 3 – 30 3 – 30
Nominal connection distance m 7 7 7 7 7 7
Pre-lledconnectiondistance m 10 10 10 10 10 10
Additionalcoolantll-upquantity(R410A) g/m 20 20 30 30 50 50
Max.heightdifferenceIU/OU m 5 5 20 20 20 20
Operating range
Outside temperature (H / K) °C -20 to 35 / 16 to 43 -20 to 35 / 16 to 43 -20 to 35 / 16 to 43 -20 to 35 / 16 to 43 -20 to 35 / 16 to 43 -20 to 35 / 16 to 43
Water outlet temperature (H / K)
°C 25 to 55 / 5 to 20 25 to 55 / 5 to 20 25 to 55 / 5 to 20 25 to 55 / 5 to 20 25 to 55 / 5 to 20 25 to 55 / 5 to 20
The COP details relate to 230 V in conformance with the EC Directives 2003/32/EC. Power details in conformance with EN 14511.
The information about the energy efciency classes is based on the ofcial ErP specications (EU Ordinance No. 811/2013, EN 14511 and EN 14825) for heat pumps, which have been in
force since 26. September 2015. The efciency classes marked with an asterisk (*) correspond to the new A+++ class to be introduced from September 2019. Other ErP relevant informa-
tion is included in the respective product data sheets.
Authorised Service Partners or installation companies can activate the cooling function via a special setting.
1 Models with “B” at the end of the model denomination have an additional circulation pump as well as a mixing valve for direct connection of a second controlled heating circuit. Moreover,
the additional PCB CZ-NS4P is included in the scope of delivery.
2 Energy efciency class scale from A++ to G.
3 Energy efciency class including controller Energy efciency class scale from A+++ to D.
4 Energy efciency class scale from A to G.