94 Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
Planning
95
Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
Planning
5.2.2.5 Assembly conditions for hydro-modules and combination hydro-modules
The assembly conditions for the hydro-module or combination hydro-module are as follows:
The hydro-module is only developed for indoor installation and may not be installed
outdoors.
The installation space must be dry and frost-free and the installation location easily
accessible for maintenance work.
Cables, pipelines and wall bushings should be arranged functionally and using the
shortest path (electrical cables, coolant and heating water pipelines).
Ensure good air circulation in the installation room.
There must not be any heat or vapour sources near the hydro-module. Even
laundries or other rooms with high humidity are not suitable, because high humidity
causes rusting and can damage the device.
The condensation from the condensation drain of the hydro-module should be able
to run without obstacles, because incorrect draining can cause damage.
Development of noise in the room should be taken into account ( 5.2.1 Acous-
tics, p. 87).
Do not mount the device near the door.
Maintain the minimum distances ( 5.2.2.6 Minimum distances for hydro-modules
and combination hydro-modules, p. 95).
The hydro-module must be installed vertically on the wall, where the wall should be
strong and solid, so that no vibration occurs.
In case electrical devices are installed on wooden buildings with metal strips or ca-
ble cleats, no electrical contacts are allowed between device and building accord-
ing to the corresponding standards for electrical work.
5.2.2.6 Minimum distances for hydro-modules and combination hydro-modules
Combination Hydro-module H-Generation
2
2
1
2
3
Minimum distances combination hydro-module
H-Generation
1 Minimum distance: 300 mm
2 Minimum distance: 100 mm
3 Minimum distance: 700 mm
Hydro-module F-Generation Hydro-module H-Generation
1
1
2
1
1
1
2
1
Minimum distances hydro-module F-Generation
1 Minimum distance: 300 mm
2 Minimum distance: 600 mm
Minimum distances hydro-module H Generation
1 Minimum distance: 100 mm
2 Minimum distance: 800 mm
!
IMPORTANT
As the compressor is in the outdoor unit of the split system, only the operation of the circulation
pump in the hydro-module or combination hydro-module needs to be taken into consideration as
the cause for the development of operating noises.