164 Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
Installation
165
Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
Installation
Allowable tightening torques of the water pipelines – hydro-module H-Generation
Model Connection
1
Size of the cap nut Torque
Nm
LT
WH-SDC03H3E5-1 + WH-UD03HE5-1
1-Waterinow
2 - Water return
Rp 1¼“ 117.6
WH-SDC05H3E5-1 + WH-UD05HE5-1
WH-SDC07H3E5-1 + WH-UD07HE5-1
WH-SDC09H3E5-1 + WH-UD09HE5-1
WH-SDC12H6E5 + WH-UD12HE5
WH-SDC16H6E5 + WH-UD16HE5
WH-SDC09H3E8 + WH-UD09HE8
WH-SDC12H9E8 + WH-UD12HE8
WH-SDC16H9E8 + WH-UD16HE8
T-CAP
WH-SXC09H3E5 + WH-UX09HE5
1-Waterinow
2 - Water return
Rp 1¼“ 117.6
WH-SXC12H6E5 + WH-UX12HE5
WH-SXC09H3E8 + WH-UX09HE8
WH-SXC12H9E8 + WH-UX12HE8
WH-SXC16H9E8 + WH-UX16HE8
WH-SQC09H3E8 + WH-UQ09HE8
WH-SQC12H9E8 + WH-UQ12HE8
WH-SQC16H9E8 + WH-UQ16HE8
1 Cfr. → Connections of the water pipelines - hydro-module H-Generation, p. 164
Compact devices
Connections of the water pipelines – Compact devices
1
2
34
5
3
Typical installation example with dirt catcher
1 Waterinow
2 Water return
3 Shut-off valve
4 Dirt catcher
5 Cap nut
Allowable tightening torques of the water pipelines – Combination hydro-module
H-Generation
Model Connection
1
Size of the cap nut Torque
Nm
LT
WH-ADC0309H3E5(B) + WH-UD03HE5-1
a - Water return
2
b-Waterinowheating
2
Rp 1¼“ 117.6
WH-ADC0309H3E5(B) + WH-UD05HE5-1
WH-ADC0309H3E5(B) + WH-UD07HE5-1
WH-ADC0309H3E5(B) + WH-UD09HE5-1
c - Water return
3
d-Waterinowheating
3
WH-ADC1216H6E5 + WH-UD12HE5
WH-ADC1216H6E5 + WH-UD16HE5
WH-ADC0916H9E8 + WH-UD09HE8
e - Fresh water
f-Waterinowhotwater
Rp ¾“ 58.8
WH-ADC0916H9E8 + WH-UD12HE8
WH-ADC0916H9E8 + WH-UD16HE8
T-CAP
WH-ADC1216H6E5 + WH-UX09HE5
c - Water return
d-Waterinowheating
Rp 1¼“ 117.6
WH-ADC1216H6E5 + WH-UX12HE5
WH-ADC0916H9E8 + WH-UX09HE8
WH-ADC0916H9E8 + WH-UX12HE8
WH-ADC0916H9E8 + WH-UX16HE8
e - Fresh water
f-Waterinowhotwater
Rp ¾“ 58.8
WH-ADC0916H9E8 + WH-UQ09HE8
WH-ADC0916H9E8 + WH-UQ12HE8
WH-ADC0916H9E8 + WH-UQ16HE8
1 Cfr. → Connections of the water pipelines - Combination hydro-module H-Generation, p. 163
2 For Version “B“ for 2. Heating circuit; not available for standard version.
3 For Version “B“ for 1. Heating circuit.
Hydro-modules
Connections of the water pipelines – hydro-module H-Generation
21
1 Waterinow 2 Water return