13.16.1.10 Human Activity Sensor Abnormality
Abnormality detection:
o Connector disconnection / Wire cut abnormality
Sensor judge Hi level continuously for 25 seconds
o Circuit abnormality
70 seconds after power ON, if human activity sensor judge Lo level continuously for 25 seconds
Error Code judgment
o When abnormality happened, internal counter increase by 1 time.
o Human activity sensor power OFF, retry after 5 seconds.
o When the human activity sensor maintains normal condition for 120 seconds, the counter reset or AC reset.
o When abnormality counter reached 4 times, No TIMER indicator blinking.
When error code happened, the unit is able to operate without AUTO COMFORT / ECONAVI.
13.16.1.11 Human Activity Sensor Check Mode
To enable human activity sensor check mode, during ECONAVI operation ON:
During ECONAVI is ON, when CHECK signal received, if either sensors has abnormality, the 4 times abnormality
counter is ignored, ECONAVI Indicator will blink immediately and error code is memorized.
The unit could operate without ECONAVI or AUTO COMFORT.
The ECONAVI indicator blinking could be cancelled by pressing ECONAVI button again.
If the human activity sensor has no abnormality, the CHECK process will end and continue with normal operation.

Table of Contents

Other manuals for Panasonic CS-A12PKD

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic CS-A12PKD and is the answer not in the manual?

Panasonic CS-A12PKD Specifications

General IconGeneral
BrandPanasonic
ModelCS-A12PKD
CategoryAir Conditioner
LanguageEnglish

Related product manuals