(*1) / Outdoor unit fan start control during cooling / At the start of cooling mode and drying
mode operation, the outdoor unit heat exchanger outlet temperature is detected in order to set
the fan speed. / Operation is carried out at the fan speed detected for 30 seconds.
After 30 seconds, the heat exchanger outlet temperature is detected and the outdoor unit fan
speed is changed automatically.
(*2) / Cooling low outdoor temperature protection / When the outlet temperature of the heat
exchanger drops to less than 12°C for a continuous period of 10 minutes, the outdoor unit stops.
/ This is cancelled after 3 minutes (re-start prevention)
- Remote control displays and indoor unit operation continue during
this time.
- The 10 minutes countdown is cleared if the compressor stops or if
the temperature at the outdoor unit outlet rises to 13.C or higher.
27.2. Drain pump control
1. Basic operation / During cooling mode, dry mode or defrost mode